Installing gateway
36/95
Potential conditions between the components
The entire SmartWire-DT system operates on a common supply voltage.
Provide a common star point for the earth wiring. In this way, the various
slaves in the SmartWire-DT system will not be electrically isolated from one
another.
The Sercos network and the SmartWire-DT system are electrically isolated
from one another.
7.4
Connecting SmartWire-DT
Ø
Connect the SmartWire-DT network to the gateway. To do so, use the
SmartWire-DT cable SWD4-100LF8-24 and the SWD4-8MF2 relevant
blade terminal or prefabricated cables of type SWD4-(3/5/10)F8-24-2S.
Figure 5: Connecting SmartWire-DT to gateway
Device destruction
Switch off the power supply before you are reconnecting slaves in the
SmartWire-DT system or reconnecting the ribbon cable connection.
Otherwise the SmartWire-DT slaves can be destroyed!
Detailed instructions on adapting the SmartWire-DT external device
plug (SWD4-8SF2-5) to the 8 pole Smart-Wire-DT cable are
provided in chapter
Fitting external device plugs SWD4-8SF2-5
of
the manual
SmartWire-DT – The System
, MN05006002Z-EN
(previously AWB2723-1617en).