Acyclical communication
58/95
2. Configure read request.
Ø
In the
IDN
field, enter
S-0-2000.1.1
then press
Enter
on your
keyboard.
Ø
Enter SWD Index in field
0
, Request Type in field
1
and the length of the
expected response in field
2
:
Figure 23: Configure read request
Ø
Press
Enter
on your keyboard.
3. Activate read request.
Ø
In the
IDN
field, enter
S-0-2000.1.3
then press
Enter
on your
keyboard.
Ø
In the
Value
field, set the last two digits to
11
.
Figure 24: Activate read request
Ø
Press
Enter
on your keyboard to issue this procedure command and
thus activate the read request on the gateway.
SmartWire-DT Gateway | EU5C-SWD-SERCOS
DOC160805UM01EN | Revision 1 | English | 2017-02 | Released | Public
© Hilscher 2017