Acyclical communication
62/95
2. Configure write request.
Ø
In the
IDN
field, enter
S-0-2000.1.1
then press
Enter
on your
keyboard.
Ø
Enter SWD Index in field
0
, Request Type in field
1,
length in field
2
and
the data to be written (the reset-value) in field
3
:
Figure 27: Configure write request
Ø
Press
Enter
on your keyboard.
3. Activate write request.
Ø
In the
IDN
field, enter
S-0-2000.1.3
then press
Enter
on your
keyboard.
Ø
In the
Value
field, set the last two digits to
11
.
Figure 28: Activate write request
Ø
Press
Enter
on your keyboard to issue this procedure command and
thus activate the write request on the gateway.
SmartWire-DT Gateway | EU5C-SWD-SERCOS
DOC160805UM01EN | Revision 1 | English | 2017-02 | Released | Public
© Hilscher 2017