Diagnosis
66/95
11.2 Diagnosis messages of individual SWD slaves (Diagnosis
Class = Warning)
11.2.1
Overview “Warning”
Diagnostic messages issued by individual SmartWire-DT devices are
reported in IDN
S-0-0390.0.0
(Diagnostic Number) as
Diagnosis Class
=
Warning
(bits 19...16 =
0x0E
).
In this case the
Status Code
contains the corresponding SmartWire-DT
diagnosis code.
The diagnosis codes of individual SmartWire-DT slaves can be
looked-up in the user manual of the corresponding device (for
devices manufactured by Eaton, for example, this would be the
manual
SmartWire-DT modules
, MN05006001Z-EN).
In case of
Diagnosis Class
=
Warning
, the IDN
S-0-0095.0.0
(Diagnostic Message) always contains the standard text
SmartWire-DT
specific diagnosis
.
The address of the concerned SmartWire-DT slave is indicated in the
Slot
Number
(Bits 23 ... 16) of the IDN
S-0-1500.0.32
(IO Diagnostic
Message).
Note:
Messages of
Diagnosis Class
=
Warning
do not need to be
acknowledged by the Sercos master. Once the cause of the
warning has been removed, the diagnosis gets cleared from the
IDNs.
SmartWire-DT Gateway | EU5C-SWD-SERCOS
DOC160805UM01EN | Revision 1 | English | 2017-02 | Released | Public
© Hilscher 2017