Specification
Value
Rated input current
24 A at -40 VDC
Rated input power (W)
874 W at -40 VDC
Rated input power (BTUs per hour)
2983 at -40 VDC
Power supply output
—
Rated steady-state power (W)
800 W at -40 VDC to -72 VDC
Maximum peak power (W)
800 W at -40 VDC to -72 VDC
Maximum peak power
800 W at 200 VAC to 277 VAC
800 W at -40VDC to -72 VDC
WARNING: To reduce the risk of electric shock or energy hazards:
• This equipment must be installed by trained service personnel.
• Connect the equipment to a reliably grounded secondary circuit source. A secondary circuit has no direct
connection to a primary circuit and derives its power from a transformer, converter, or equivalent isolation
device.
• The branch circuit overcurrent protection must be rated 27 A.
CAUTION: This equipment is designed to permit the connection of the earthed conductor of the DC supply circuit
to the earthing conductor at the equipment.
If this connection is made, all of the following must be met:
• This equipment must be connected directly to the DC supply system earthing electrode conductor or to a
bonding jumper from an earthing terminal bar or bus to which the DC supply system earthing electrode
conductor is connected.
• This equipment must be located in the same immediate area (such as adjacent cabinets) as any other
equipment that has a connection between the earthed conductor of the same DC supply circuit and the earthing
conductor, and also the point of earthing of the DC system. The DC system must be earthed elsewhere.
• The DC supply source is to be located within the same premises as the equipment.
• Switching or disconnecting devices must not be in the earthed circuit conductor between the DC source and the
point of connection of the earthing electrode conductor.
Specifications
147
Содержание ProLiant DL20 Gen10
Страница 24: ...Customer self repair 24 ...
Страница 25: ...Customer self repair 25 ...
Страница 26: ...Customer self repair 26 ...
Страница 138: ...Controller backup power cabling Slot 1 Slot 2 Cabling 138 ...