Temperature manager
8
19
If there is no buffer in the system, then the MUST-temperature from the individual modules is determined and
to that an adjustable temp. increase is added. The highest of these temperatures is the boiler-MUST-
temperature. To this an adjustable hysteresis is added and the result is the boiler-END-temperature (see fig.
8.4). Caution: Consider the set minimum requirement.
Fig 8.4: Example temperature manager when operation without buffer
If a time mode is applied directly on the buffer, then the required buffer-top-temperature is set directly in the
time mode module. Now it must be distinguished again if the buffer-top-temperature is higher than the
adjusted buffer-bottom-MUST-temperature. In this case the required boiler temperature is the result of the
required buffer-bottom-MUST-tempe the adjusted temp. in the adjusted difference (see fig.
8.5). If this is not the case, the required boiler temperature is the result of the required temperature + the
adjusted temp. increase (see 8.6). Caution: Consider the set minimum requirement.
Fig 8.5: Example temperature manager when time mode with difference
Содержание pelletstar CONDENSATION 10
Страница 1: ...OPERATING INSTRUCTIONS Pellet boiler pelletstar CONDENSATION 10 60 ...
Страница 20: ...8 Temperature manager 20 Fig 8 6 Example temperature manager when time mode without difference ...
Страница 85: ...Annex 15 85 15 ANNEX 15 1 Additional boiler schematic visualization Hydraulic recommendation 1 ...
Страница 86: ...15 Annex 86 Hydraulic recommendation 2 ...
Страница 87: ...Annex 15 87 15 2 Solar module schematic representation Program 1 ...
Страница 88: ...15 Annex 88 Program 2 ...
Страница 89: ...Annex 15 89 Program 3 ...
Страница 90: ...15 Annex 90 Program 4 ...
Страница 91: ...Annex 15 91 Program 5 ...
Страница 92: ...15 Annex 92 Program 6 ...
Страница 93: ...Notes 16 93 16 NOTES ...