11
Description of the menu navigation and adjustment values
50
Betriebsanleitung_pelletfire_Touch_Englisch_V1.2
Term
Description
Unit
Status I
Collector flow
temperature
Displays the collector flow temperature
°C
Collector backflow
temperature
Displays the collector backflow temperature
°C
Tank 1 temperature
Displays the temperature of tank 1 (e.g.: hot water tank, buffer)
°C
Tank 2 temperature
Displays the temperature of tank 2 (e.g.: hot water tank, buffer)
(only visible, if program 3, 4, 5 or 6 is chosen)
°C
Status II
Actual yield
Indication of the current energy yield
W
Daily yield
Indication of the energy yield on one day (from 0
– 24h)
Wh
Total yield
Indication of the total energy yield measured
kWh
Collector pump
Indication of the state of the collector pump
-
Loading pump
Indication of the state of the loading pump
only visible, if program number 2 or 6 is chosen
-
Switching valve
Indication of the state of the switching valve
only visible, if program number 3,4,5 or 6 is chosen
-
Settings I
Program number
Indicates the program number (1 to 6)
-
Antifreeze
Outside temperature setting (-45 to 5) which conducts a permanent
running of the solar pump to avoid freezing.
°C
Flow rate
Flow rate setting (0-99,9) for calculating solar output resp. for
calculating the yield
l/min
Rotation speed control
Activation of speed regulation (ON/OFF)
-
Min. rotation speed
Setting up minimum rotation speed (20-100) of the solar pump
%
Must value
Setting up rotation speed set point of solar pump
°C
Control difference
Setting up the control difference of the rotation speed control (if active)
°C
Settings II
Pump trigger
Setting up minimum collector temperature (15-70) to start up the solar
pump
°C
Tank 1 must
temperature
Setting up must temperature (25-90) of tank 1
°C
Difference 1
Difference between collector and tank 1
°C
Tank 1 max.
temperature
Setting up maximum temperature (25-95) of tank 1
°C
Tank 2 must
temperature
Setting up must temperature (25-90) of tank 1
(
only visible, if program number 3, 4, 5 or 6 is chosen)
°C
Difference 2
Setting up the difference (5-30) between collector and tank 1
(
only visible, if program number 3, 4, 5 or 6 is chosen)
°C
MODUL
Boiler
Buffer
Hot water tank
Heating circuit
Time mode
Solar
Hydr.compensat
Net pump
Zone valve
Ext. requirement
addit. boiler
Содержание pelletfire
Страница 1: ...Operating instructions Log Wood Pellet heatingsystem pelletfire 20 40 ...
Страница 86: ...16 Annex 86 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 Hydraulic recommendation 2 ...
Страница 87: ...Annex 16 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 87 16 2 Solar module Program 1 ...
Страница 88: ...16 Annex 88 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 Program 2 ...
Страница 89: ...Annex 16 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 89 Program 3 ...
Страница 90: ...16 Annex 90 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 Program 4 ...
Страница 91: ...Annex 16 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 91 Program 5 ...
Страница 92: ...16 Annex 92 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 Program 6 ...
Страница 93: ...Notes 17 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 93 17 NOTES ...
Страница 94: ...17 Notes 94 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 ...
Страница 95: ...Notes 17 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 95 ...