Fault reports and their correction
12
Betriebsanleitung_pelletfire_Touch_Englisch_V1.2
75
Nr. Fault text
Reason
Suggestions for rectifying
083
GRATE CLEANING 2
Failure grate cleaning; impossible to
close grate; grate got stuck; grate
linkage damaged or loosened
Remove debris
Check grate cleaning motor
Check grate linkage
Check grate cleaning end switch
✆
- contracting party
084
GRATE CLEANING 3
Grate was opened during the
combustion
Check grate cleaning motor
Check grate linkage
Check grate cleaning end switch
085
SUCTION MODE
Fault in pellet feed system
Pellet store empty
Vacutrans valve out of position
Vacutrans valve gasket defective
Leak in pellet feed hose
Suction air hose leaking or loose
Suction turbine defective
Adjust suction cycles
Check discharge system (motor,
screw)
Check fuel quality
086
SUCTION VALVE
Empty level container at compact
container
Check vacutrans damper
Check end switch vacutrans
damper
✆
- contracting party
087
ASH CONTAINER
Ash container door open
Connect ash container
Close ash container door
090
COMB. ROOM SENSOR
End switch of the combustion room
door has been activated
–
Combustion chamber door is open
Close combustion chamber door
091
WARNING ASH
DISCHARGE
Ash discharge has not been
cleaned or does not rotate
Ash container is full
Foreign bodies are blocking the
screw
Motor is defect
Empty the ash container
Remove foreign bodies
092
ERROR ASH
DISCHARGE
Ash discharge has not cleaned for
several times -> system turns off
Ash container is full
Foreign bodies are blocking the
screw
Motor is defect
Empty the ash container
Remove foreign bodies
✆
-
contracting party
093
ENDSW. ROOM
DISCHARGE
Endswitch room discharge has been
activated
Blackage; remove trapped fuel
Check fuel quality
Clean intermediate hopper level
sensor
094
AUTO. IGNITION
Fault automatic ignition
Check fuel quality
Use dry log wood
Clean burner plate holes
095
CHECK ASH BOX
Interval for checking the ash box is
exceeded
Check ash box and empty as
needed
096
BURNER STOP
System is situated on “Burner Stop” -
111
HEAT EXCHANGER
Heat exchanger cleaning does not
work, heatexchanger motor does
not work
Check heat exchanger cleaning
Manual cleaning of the heat
exchanger; check plug of the heat
exchanger; change heat
exchanger motor
Содержание pelletfire
Страница 1: ...Operating instructions Log Wood Pellet heatingsystem pelletfire 20 40 ...
Страница 86: ...16 Annex 86 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 Hydraulic recommendation 2 ...
Страница 87: ...Annex 16 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 87 16 2 Solar module Program 1 ...
Страница 88: ...16 Annex 88 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 Program 2 ...
Страница 89: ...Annex 16 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 89 Program 3 ...
Страница 90: ...16 Annex 90 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 Program 4 ...
Страница 91: ...Annex 16 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 91 Program 5 ...
Страница 92: ...16 Annex 92 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 Program 6 ...
Страница 93: ...Notes 17 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 93 17 NOTES ...
Страница 94: ...17 Notes 94 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 ...
Страница 95: ...Notes 17 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 95 ...