10
Fault reports and their corrections
68
No. Fault report
Cause of fault
Fault correction
056
SCREED BAKE OUT
Failure at screed bake out; Flow set
temperature could not be reached
▪
Function check mixer with mixer
motor
▪
Function check pump
▪
Check sensor position
▪
Required heat output to high
057
CHECK DATA MODUL
Module parameter is not in the
specified range
▪
Restart T-Control
▪
Check boiler parameter
058
CHECK DATA BOILER
Boiler parameter is not in the
specified range
▪
Restart T-Control
▪
Check boiler parameter
059
CAN-ID
Set up module CAN-ID not useable
-
069
STL
Boiler temperature has exceeded
the maximum permissible boiler
temperature
▪
Cool down boiler (< 75 °C)
▪
Quit STL
071
LAMBDA FUEL
Failure lambda probe
✆
- contracting party
072
CAN FAULT
Failure CAN bus
✆
- contracting party
073
LAMBDA
CALIBRATION
Failure during lambda probe
calibration
✆
- contracting party
081
SPEED ID-FAN
Failure rotation speed ID fan
▪
Check connection rotation speed
sensor
▪
Check ID-fan
▪
✆
- contracting party
088
BACK FLOW SET
PWM
if PWM module is not recognized
▪
Burn out and boiler off
▪
acknowledges itself
090
COMB. ROOM
SENSOR
Burning chamber door end switch
active; burning chamber door is
open
Close burning chamber door
094
AUTO IGNITION
Fault automatic ignition
Boiler could not ignite in the set time
▪
Check fuel quality
▪
Use dry log wood
▪
Clean burner plate holes
097
Backup config
Fault when loading backup
✆
- contracting party
111
HEAT EXCHANGER
CLEANING
Heat exchanger cleaning does not
work
Heat exchanger motor does not
work
▪
Check heat exchanger cleaning
▪
Manual cleaning of the heat
exchanger
▪
plug loud Check Electro
documentation
▪
change heat exchanger motor
180
KAS CHKDATA
Cascade parameter is not in the
specified range
▪
Restart T-Control
▪
Check cascade parameter
181
KAS CONNECTION
No connection to cascade
Check cascade connection
182
KAS OFFLINE
Boiler is not available to cascade
Establish data connection
189
KAS ALARM
Leading boiler couldn't be started or
got stopped
▪
Start leading boiler
▪
✆
- contracting party
190
DATAERROR
MEMORY BOILER-
MODULE
Error when synchronizing boiler
extension module
✆
- contracting party
Содержание firestar de Luxe 18
Страница 1: ...OPERATING INSTRUCTIONS Log wood boiler firestar de Luxe 18 40 ...
Страница 18: ...8 Temperature manager 18 Fig 8 6 Example temperature manager when time mode without difference ...
Страница 80: ...16 Annex 80 16 ANNEX 16 1 Additional boiler module Hydraulic recommendation 1 ...
Страница 81: ...Annex 16 81 Hydraulic recommendation 2 ...
Страница 82: ...16 Annex 82 16 2 Solar module Program 1 ...
Страница 83: ...Annex 16 83 Program 2 ...
Страница 84: ...16 Annex 84 Program 3 ...
Страница 85: ...Annex 16 85 Program 4 ...
Страница 86: ...16 Annex 86 Program 5 ...
Страница 87: ...Annex 16 87 Program 6 ...
Страница 88: ...17 Notes 88 17 NOTES ...
Страница 89: ...Notes 17 89 ...