Fault reports and their corrections
66
No. Fault report
Cause of fault
Fault correction
022
SENSOR SOLAR
Failure solar tank temperature
sensor (hot water tank/buffer)
▪
Check sensor, replace as necessary
▪
Check plug, replace as necessary
▪
Check wiring incl. connections,
replace as necessary
▪
✆
- contracting party
023
ADDITIONAL BOILER
SENSOR
Failure additional boiler sensor;
cable break; short-circuit; failure
connection
▪
Check sensor, replace as necessary
▪
Check plug, replace as necessary
▪
Check wiring incl. connections,
replace as necessary
▪
✆
- contracting party
024
MODUL SENSOR
Failure modul temperature sensor;
cable break; short-circuit; failure
connection
▪
Check sensor, replace as necessary
▪
Check plug, replace as necessary
▪
Check wiring incl. connections,
replace as necessary
▪
✆
- contracting party
025
OVERHEAT BOILER
MAX
Boiler temperature exceeded 98 °C
▪
Check settings
▪
Check back flow mixer
▪
Check back flow pump
026
OVERHEAT
Boiler temperature exceeded 92 °C
▪
Check settings
▪
Check back flow mixer
▪
Check back flow pump
027
SOLAR
OVERHEATING
Fault is shown, if collector
temperature exceeds 140°C
▪
Check solar pump
▪
Check solar tank level
028
SOLAR MAX.
LOADING
collector temperature exceeds 120
°C
Check solar pump
Check solar tank level
029
ANTIFREEZE BOILER
Boiler temperature respectively
operation room temperature under 7
°C
Check or increase the room
temperature in the boiler room.
030
ANTIFREEZE BUFFER
Buffer bottom sensor temperature
under 7 °C
Check or increase the room
temperature in the boiler room.
031
ANTIFREEZE HOT
WATER TANK
Hot water tank under 7 °C
Check or increase the room
temperature in the boiler room.
032
ANTIFREEZE
HEATING CIRCUIT
Heating circuit flow- or heating
circuit back flow temperature under
7 °C
Check or increase the room
temperature in the boiler room.
033
ANTIFREEZE SOLAR
Collector temperature under set up
antifreeze temperature
-
034
ANTIFREEZE HYDR.
COMPENSATOR
Hydraulic compensator temperature
under 7 °C
Check or increase the room
temperature in the boiler room
035
ANTIBLOCKING BACK
FLOW
Back flow antiblocking active, back
flow pump gets triggered 10
seconds
-
036
ANTIFR. ADD. BOILER
Additional boiler temperature under
7 °C
Check or increase the room
temperature in the boiler room
037
HOT WATER TANK
LOADING
Hot water tank didn´t reach set
temperature during loading time; hot
water tank loading gets blocked till
fault correction
▪
Adapt loading time
▪
Activate hot water tank priority
▪
Hot water tank settings (min./ must)
Содержание firestar de Luxe 18
Страница 1: ...OPERATING INSTRUCTIONS Log wood boiler firestar de Luxe 18 40 ...
Страница 18: ...8 Temperature manager 18 Fig 8 6 Example temperature manager when time mode without difference ...
Страница 80: ...16 Annex 80 16 ANNEX 16 1 Additional boiler module Hydraulic recommendation 1 ...
Страница 81: ...Annex 16 81 Hydraulic recommendation 2 ...
Страница 82: ...16 Annex 82 16 2 Solar module Program 1 ...
Страница 83: ...Annex 16 83 Program 2 ...
Страница 84: ...16 Annex 84 Program 3 ...
Страница 85: ...Annex 16 85 Program 4 ...
Страница 86: ...16 Annex 86 Program 5 ...
Страница 87: ...Annex 16 87 Program 6 ...
Страница 88: ...17 Notes 88 17 NOTES ...
Страница 89: ...Notes 17 89 ...