8
Temperature manager
16
If the required buffer-top-temperature (required temperature) is higher than the sum of buffer-bottom-MUST-
temperature and the set difference, then the required boiler temperature is the result of the required buffer-
top-temperature (required temperature) + the adjusted temp. increase (see Fig.8.2). Caution: Consider the
set minimum requirement.
Fig.8.2: Example temperature manager with buffer and without difference
If the required buffer-top-temperature (required temperature) is lower than the buffer-bottom-MUST-
temperature than the required boiler temperature is the result of the required buffer-bottom-temperature +
the adjusted temp. increase + the adjusted difference (see Fig. 8.3). Caution: Consider the set minimum
requirement.
Fig. 8.3: Example temperature manager with buffer and difference
Содержание firestar de Luxe 18
Страница 1: ...OPERATING INSTRUCTIONS Log wood boiler firestar de Luxe 18 40 ...
Страница 18: ...8 Temperature manager 18 Fig 8 6 Example temperature manager when time mode without difference ...
Страница 80: ...16 Annex 80 16 ANNEX 16 1 Additional boiler module Hydraulic recommendation 1 ...
Страница 81: ...Annex 16 81 Hydraulic recommendation 2 ...
Страница 82: ...16 Annex 82 16 2 Solar module Program 1 ...
Страница 83: ...Annex 16 83 Program 2 ...
Страница 84: ...16 Annex 84 Program 3 ...
Страница 85: ...Annex 16 85 Program 4 ...
Страница 86: ...16 Annex 86 Program 5 ...
Страница 87: ...Annex 16 87 Program 6 ...
Страница 88: ...17 Notes 88 17 NOTES ...
Страница 89: ...Notes 17 89 ...