HelmPak Press Control
20
Users Guide
SECTION 5:
System Setup
On the main System Setup screen, the user has 5 entry options, 4 page buttons, and an exit to
configuration screen button. The Exit to Configuration screen button exits out of the current running
application, to the built in HMI interface.
Resolver Setup
This is used to calibrate the resolver input module during initial installation.
Move the crank position to 0 degrees and press Zero Resolver.
Calibrate the resolver input module in both PLC A & PLC B processors.
DM Inch Bypass
This buttons will allow Die Monitoring Inch Bypass to be enabled or disabled ( Enabled by Default)
Inch Stop On Top
This buttons will allow Inch Stop On Top to be enabled or disabled (disabled by Default)
Top Stop Setup
Run the press at maximum speed.
Enter the arbitrary number into the minimum angle. (350)
Run a Single stroke.
Add or subtract the top stop angle value to get an accurate top stop and enter that value into the top stop
angle.
For instance if the press stops at 30
°
, Subtract 30 from the top stop and enter that value of
350(350-30=320). Enter 320 into the minimum angle.
Brake Monitor Setup
Shows the brake stop time in milliseconds and brake fault preset time, which is the amount of time in
milliseconds allowed before the system alarms on a brake fault time fault.