34
Heat-Timer Corp.
• Manual Valve
- The SQ-Elite-MV will only control the motorized valve if the valve was set to Auto. Check to see if the valve is set
to On. See Valve on page
.
• Gain
- View the MOV Sensor history, if the temperature tends to oscillate, reduce the Gain. See Gain on page
.
• Sensor Fault
- If MOV Sensor Fault is set to Valve Open and the Outdoor or MOV System sensor reads
Short
or
Open
, the
SQ-Elite-MV will change the MOV Target to the Maximum Water temperature or open the valve. Check the Outdoor and MOV
System Sensor readings. See MOV Sensor Fault on page
too little seQ Heat
Check if the control has any of the following:
• Reset Ratio and Offset
- If reduced heat occurs only in certain weather conditions, adjust the SEQ Reset Ratio and Offset (See
Understanding Operating Concept on page
). If it occurs year round, increase the SEQ Offset. See SEQ Offset on page
.
• Setback and Day/Night Schedule
- If reduced heat occurs during Night hours, reduce the SEQ Setback setting. See SEQ Setback
. If the building takes a long time to recover from the Night period, increase the SEQ Boost or Boost Period. See SEQ
• Boiler Mode Settings
- If the decreased heat occurs under extreme cold weather conditions, check if any boiler Mode is set to Off,
or Standby. The SQ-Elite-MV will only sequence boilers their mode is set to Auto or Standby. See Boiler Mode on page 3
• Sensor Fault
- If SEQ Sensor Fault is set to Stages Off and the Outdoor or SEQ System sensor reads
Short
or
Open
, the
SQ-Elite-MV will change the SEQ Target to the Minimum Water temperature or de-energize all boiler stages. Check the Outdoor
and SEQ System Sensors. See SEQ Sensor Fault on page
.
too little MoV Heat
Check if the control has any of the following:
• Reset Ratio and Offset
- If reduced heat occurs only in certain weather conditions, adjust the MOV Reset Ratio and Offset (See
Understanding Operating Concept on page
). If reduced heat occurs year round, increase the MOV Offset. See MOV Offset on
• Setback and Day/Night Schedule
- If reduced heat occurs during Night hours, reduce the MOV Setback setting. See MOV
Setback on page 28
. If the building takes a long time to recover from the Night period, increase the MOV Boost or Boost Period.
See MOV Boost on page 28.
• Gain
- View the MOV Sensor history, if the temperature tends to hover below the MOV Target, increase the Gain. See Gain on
• Sensor Fault
- If MOV Sensor Fault is set to Valve Close and the Outdoor or MOV System sensor reads
Short
or
Open
, the
SQ-Elite-MV will change the MOV Target to the Minimum Water temperature. Check the Outdoor Sensor. See MOV Sensor Fault
.
no Heat
Check if the control has any of the following:
• Season
- If the Season is set to Summer, all boiler stages will be off and the motorized valve will be closed. See Season on page 22.
• Sensor Fault
- If SEQ or MOV Sensor Fault is set to Valve Close or Stages Off and the respective system sensor reads
Short
or
Open
, the boilers might all be off on the SEQ System Sensor fault. Or, the motorized valve will be closed on a MOV System
Sensor fault. See SEQ Sensor Fault on page 2
and MOV Sensor Fault on page 2
• Shutdown
- If External Input 1 is configured as a Shutdown and the terminals were shorted/activated, all stages will be off and the
motorized valve will close. See External Input 1 on page 19
• SEQ Tstat
- If External Input 1 is configured as a SEQ Tstat and the terminals were Open/deactivated, all stages will be off. See
External Input 1 on page 19
• MOV Tstat
- If External Input 2 is configured as a MOV Tstat and the terminals were Open/deactivated, the motorized valve will
closed. See External Input 2 on page
• Prove
- If External Input 2 was set as SEQ Prove and no wiring is attached to the Prove terminals all boilers will be off. See
External Input 2 on page
• Manual Valve
- The SQ-Elite-MV will only control the motorized valve if the valve was set to Auto. Check to see if the valve is set
to Off. See Valve on page
• Boiler Mode Settings
- Check if any boiler Mode is set to Off, or Standby. The SQ-Elite-MV will only sequence boilers their mode
is set to Auto or Standby. See Boiler Mode on page 3