background image

SQ-Elite-MV & SQ-Elite-EXT Installation Manual 

 31

dIsplay BoIler status

The display bottom line gives immediate access to each boiler status.  The following list shows all possible boiler status:

•   <AB>   Two-Stage boiler and Boiler AB is the Lead in sequencing. (Brackets indicate Lead Stage).

•   --- 

 Boiler stages are de-energized.  The boiler Mode is set to Auto.

•   STB   Boiler stages are de-energized.  The boiler Mode is set to Standby.

  See Mode on page 

3

2.

•   HI 

 Boiler highest stage is active.  The boiler Mode is set to either Auto or Standby.

•   MED   Boiler Middle stage is active. Available in Three-stage boilers only.  The boiler Mode is set to either Auto or Standby.

•   MHI   Boiler Middle High stage is active. Available in Four-stage boilers only.  The boiler Mode is set to either Auto or Standby.

•   MLO   Boiler Middle Low stage is active. Available in Four-stage boilers only  The boiler Mode is set to either Auto or Standby.

•   LO 

 Boiler Lowest stage is active.  The boiler Mode is set to either Auto or Standby.

•   ON   All Boiler Stages are set to ON using the Mode.  See Mode on page 3

2.

•   OFF   All Boiler Stages are set to OFF

 using the Mode.  This must be the setting for nonexisting boilers. See Mode on page 

3

2.

•   C/E   Boiler on Extension panel is not communicating back to the SQ-Elite-MV.

•     

 Boiler Pumps are being controlled by the SQ-Elite.  See Boiler Output on page 19

.

•     

 Boiler Valves are being controlled by the SQ-Elite.

  See Boiler Output on page 

19

.

dIsplay Messages

The SQ-Elite-MV normal display layout reserved the second and third lines for message indications.  The following is a list of the 

most common Message Display Line information:

SEQ Messages

•   Summer 

 The control is set to Summer.  No heat is active.

  See Season on page 22.

•   SEQ Outdoor Cutoff 

 The Outdoor temperature is above the SEQ Outdoor Cutoff.

  See Outdoor Cutoff on page 2

3

.

•   Shutdown Active 

 The Shutdown Terminals are Shorted.  No heating boilers will be active the motorized valve will be 

closed.  See Shutdown on page 

10

.

•   SEQ Shutdown by EMS 

 The EMS is below 2mA or above 22mA. All boilers will be inactive.  See Setting 4-20mA on page 1

8.

•   DHW Call (200˚F) 

 There is a DHW (Domestic Hot Water) call. The SQ-Elite-MV will Raise the SEQ Set Point to the 

indicated temperature.  DHW increases calculated temperature to the lower of 200˚F or Max Water.

•   Holding Return at 110˚F 

 The Return sensor is reading less than the Minimum Return.  SQ-Elite-MV is trying to raise return to 

110˚F.  See Boiler Minimum Return on page 

25.

•   Holding Until 150˚F 

 The Lead boiler is in Last Stage Hold.  This example shows that the lead stage will turn off when 

system temperature reaches 150˚F.  See Last Stage Hold on page 

2

6

.

•   SEQ Prove Failure 

 After boilers have run for a while, Prove signal was opened.  The boiler relays will de-energize.  

However, the System relay will remain energized.  See External Input 2 on page 19

.

•   Waiting for SEQ Prove 

 Boilers have not been running, the Prove signal is opened.  However, the System relay will remain 

energized.  See External Input 2 on page 

19

.

•   SEQ Tstat Open 

 No call for SEQ heat is activated on terminals 

35 and 36

.  See External Input 1 on page 19

.

•   All Stages On/Off 

 SEQ Sensor is reading fault.  See SEQ Sensor Fault on page 

2

0

.

•   OD Failure (240˚F) 

 Outdoor sensor is reading fault.  SEQ Sensor Fault is set to Stages On.  The control will maintain 

Maximum Water Temperature.  See SEQ Sensor Fault on page 

2

0

.

•   Boost to 170˚F 

 The SEQ Target has been increased to 170˚F to meet the Boost demand after the Setback period.  See 

SEQ Boost on page 28.

•  Setback to 150˚F 

 The SEQ Target has been decreased by the Setback to 150˚F.  See Setback Schedule on page 

28.

MOV Messages

•  Valve Close 

 The control is set to Summer or Shutdown.  No heat is active.  See Season on page 

22.

•  Manual Valve Close/Open   The valve is set manually to Close or Open.  See Valve on page 30

.

•  MOV Tstat Open 

 No call for MOV heat is activated on terminals 

37 and 38

.  See External Input 2 on page 

19

.

•  MOV Outdoor Cutoff 

 The Outdoor temperature is above the MOV Outdoor Cutoff.  See Outdoor Cutoff on page 

2

3

.

•  Fail Valve Close/Open 

 MOV Sensor is reading fault.  See MOV Sensor Fault on page 

2

1

.

•   MOV OD Failure (240˚F)   Outdoor sensor is reading fault.  MOV Sensor Fault is set to Valve Open.  The control will maintain 

Maximum Water Temperature.  See MOV Sensor Fault on page 

2

1

.

•   MOV Boost to 170˚F 

 The MOV Target has been increased to 170˚F to meet the Boost demand after the Setback period.  See 

MOV Boost on page 28.

•  MOV Setback to 150˚F 

 The MOV Target has been decreased by the Setback to 150˚F.  See Setback Schedule on page 

28.

Содержание SQ-Elite-EXt

Страница 1: ...CONTROL MOV CLOSE INPUT RATINGS 120VAC 60Hz 12VA MAX Use Copper Conductors Only CAUTION Risk of Electric Shock PWR L N 1 2 SENSORS MUST BE GOLD SERIES MOV SYS 3 MOV CLOSE 5 Stage A 7 Stage B 9 Stage C...

Страница 2: ...g settings 22 Program Change Settings 22 Season 22 seQ and MoV reset ratio settings 22 SEQ and MOV Reset Ratio 22 SEQ and MOV Customized Reset Ratio 22 SEQ and MOV Target Offset 23 SEQ and MOV Outdoor...

Страница 3: ...2A 120VAC MAXIMUM 15A TOTAL FOR ALL CIRCUITS 23 24 MOV OPEN DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS MOV OPEN MOV SYS SEQ Temp ENCLOSED ENERGY MANAGEMENT EQUIPMENT LISTED 99RA C US Press any button...

Страница 4: ...s to quickly make changes to any system setting without having to learn any specialized codes or keyboard commands Two separate menus has been provided One for the installer having all the functions W...

Страница 5: ...this means the temperature has fallen 20 from the starting point of 70 F Therefore the heating water temperature will increase 20 to 120 F Each building has different heat loss characteristics A very...

Страница 6: ...eset or by maintaining an adjustable Set Point The Outdoor Reset option uses an Outdoor Sensor supplied with the control and achieves better fuel savings in addition to better comfort Using an optiona...

Страница 7: ...inals This switch is enclosed with the enclosure wiring cover for security Wiring terminals are of the plug in type to ease installation and removal The Enclosure Base contains the holes to mount and...

Страница 8: ...or Shield alert If any of the System Sensors cannot sense the correct system water temperature the SQ Elite MV will not provide comfortable heat levels outdoor sensor InstallatIon Only use the Heat Ti...

Страница 9: ...temperature Whether in Set Point or Outdoor Reset modes the outdoor sensor can be used as an Outdoor Cutoff The SQ Elite MV will disable all Boilers and close the motorized valve when the outdoor tem...

Страница 10: ...V will sequence the stages to achieve the desired SEQ Set Point However when the terminals are opened all stages will de energize The Tstat signal must be a dry contact only No voltage can be placed a...

Страница 11: ...DHW during Summer or when SEQ Tstat input is opened DHW PUMP 13 Stage E 15 Stage F 17 12 14 16 18 19 SEQ SYS SEQ System Pump L N wIrIng tHe MoV systeM output terMInals 19 20 Connect the MOV pump Motor...

Страница 12: ...igher stage of the same boiler must be connected to Stage B The boiler valve or pump must be connected to Stage C PWR L N 1 2 3 5 Stage A 7 Stage B 9 Stage C 11 13 Stage E 15 Stage F Stage D 6 8 10 12...

Страница 13: ...Two Extension Panels and 4 20mA EMS Interface using RS485 SQ Elite MV SQ Elite MV SEQUENCING CONTROL INPUT RATINGS 115VAC 60Hz 12VA MAX Use Copper Conductors Only CAUTION Risk of Electric Shock Stage...

Страница 14: ...Stages On Stages Off BACK SAVE ARE YOU SURE No Yes BACK SAVE eMs set poInt MAINTENANCE Unit F Present Time12 30P Valve Sensor Trim Histories Configuration BACK SELECT SENSOR TRIM SEQ Trim 0 F Outdoor...

Страница 15: ...00 SYS 12 1 00 OD 4 00 SYS BACK SAVE SEQ OUTDOOR RESET Reset Ratio 7 Target Offset 0 F Outdoor Cutoff 70 F Min Target 80 F Max Target 240 F BACK SELECT TARGET OFFSET 0 F BACK SAVE MIN TARGET 80 F BACK...

Страница 16: ...ings Setback Schedule DHW Prior Timer No Run On 2m Pump Exercise Off BACK SELECT STAGE SETTINGS Reaction Time 1min Purge Delay 0 0min Min Runtime 2min Standby Delay10min Last Stge Hold 5 F Throttle 2...

Страница 17: ...1 50 OD 1 00 SYS 6 1 25 OD 1 00 SYS 7 1 00 OD 1 00 SYS 8 1 00 OD 1 25 SYS 9 1 00 OD 1 50 SYS 10 1 00 OD 2 00 SYS 11 1 00 OD 3 00 SYS 12 1 00 OD 4 00 SYS BACK SAVE MOV OUTDOOR RESET Reset Ratio 7 Targe...

Страница 18: ...y of displaying temperature information and settings in either F Fahrenheit or C Celsius Select the display unit that is best suited for your application DISPLAY UNIT F C BACK SAVE settIng tHe 4Ma and...

Страница 19: ...ized If SEQ Prove is selected make sure to connect those terminals to either a flow switch that checks the SEQ System pump operation or a combustion air damper end switch Otherwise install a jumper on...

Страница 20: ...he following are the settings that directly affects this modes operation Reaction Time Hold Button MENU SEQ Settings System Settings Stage Settings Reaction Time Purge Delay Hold Button MENU SEQ Setti...

Страница 21: ...et to the MOV Maximum Target set poInt Mode If Valve Close is selected the SQ Elite MV will energize the MOV Close relay when the SEQ System sensor reads Short or Open If Valve Open is selected the SQ...

Страница 22: ...g Outdoor Rst Reset Ratio SEQ Hold Button MENU MOV Setting Outdoor Rst Reset Ratio MOV The Reset Ratio determines how the System water temperature will vary with outside temperature changes With any o...

Страница 23: ...ding Operation Concept on page 5 The Minimum and Maximum Target will take precedence over the Offset That is if the Max Target was set to 180 F and the Offset was set to 20 F If the set point was 170...

Страница 24: ...EQ System temperature around the SEQ Set point If the EMS Mode was Enabled the Set Point will be set by the EMS BMS system and will be available as a read only The range of Set Point in the EMS is set...

Страница 25: ...URGE DELAY 0 0min BACK SAVE The Purge Delay helps prevent short cycling of a newly activated boilers Once the lowest boiler stage is activated it MUST run through the entire Purge Delay period The min...

Страница 26: ...ng range as a differential The last stage to be turned off will be allowed to exceed the Set Point by a full Throttle before it is turned off This helps prevent the last stage from short cycling when...

Страница 27: ...he automatic rotation is recommended for most applications The current Lead Boiler is shown in brackets on the main display Only boilers which are set to Auto Mode can be Lead Therefore not all the bo...

Страница 28: ...ost will take place after the Setback is deactivated If 0 F Was selected no boost will take place seQ and MoV Boost perIod Adjustable 0 to 120 minutes Default 0 minutes Hold Button MENU SEQ Settings S...

Страница 29: ...30min BACK SAVE Priority period If NO was selected both DHW Pump and System relay will be energized on a DHW call whenever there is a DHW call during Winter In Summer or SEQ Outdoor Cutoff a DHW call...

Страница 30: ...that time and read the upper left temperature SEQ 120 F 10 00AM BACK NEXT The first screen will be the SEQ System Temperature History By clicking on the Next button you ll be able to view the Outdoor...

Страница 31: ...the SEQ Set Point to the indicated temperature DHW increases calculated temperature to the lower of 200 F or Max Water Holding Return at 110 F The Return sensor is reading less than the Minimum Retur...

Страница 32: ...o active boilers Any output without an active boiler must be set to Off The following list describes the MODE options BOILER AB MODE Auto Standby Off On BACK SAVE Auto The SQ Elite MV will control the...

Страница 33: ...st and Boost Period values Reduce the Boost amount or Boost Period setting See Boost on page 28 Boiler Mode Settings The SQ Elite MV will only sequence boilers their mode is set to Auto or Standby Che...

Страница 34: ...set See MOV Offset on page 23 Setback and Day Night Schedule If reduced heat occurs during Night hours reduce the MOV Setback setting See MOV Setback on page 28 If the building takes a long time to re...

Страница 35: ...r continuity across terminals 23 and 24 Otherwise the SQ Elite MV may be damaged Boilers are short cycling Minimum Runtime Increase the Minimum Runtime only if all boilers tend to short cycle Last Sta...

Страница 36: ...Temp Outdoor Temp MOV CLOSE SEQ SYS DHW PUMP MOV OPEN SEQ SYS SENSORS MUST BE GOLD SERIES DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS Use Copper Conductors Only CAUTION Risk of Electric Shock PROGRAM...

Страница 37: ...37 38 SEQ PROVE MOV TSTAT 23 24 MOV OPEN SEQ Temp Outdoor Temp MOV CLOSE SEQ SYS DHW PUMP MOV OPEN SEQ SYS SENSORS MUST BE GOLD SERIES DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS Use Copper Conductors...

Страница 38: ...ROVE MOV TSTAT 23 24 MOV OPEN SEQ Temp Outdoor Temp MOV CLOSE SEQ SYS DHW PUMP MOV OPEN SEQ SYS SENSORS MUST BE GOLD SERIES DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS Use Copper Conductors Only CAUTI...

Страница 39: ...age C 11 13 Stage E 15 Stage F 17 Stage D 6 8 10 12 14 16 18 RS485 4 SEQ SYS 19 DHW PUMP 21 27 29 31 MOV Temp 33 SHUTDOWN TSTAT SETBACK 35 Return Temp 20 22 28 30 32 34 36 25 26 DHW 37 38 SEQ PROVE MO...

Страница 40: ...00 SYS 3 3 00 OD 1 00 SYS 4 2 00 OD 1 00 SYS 5 1 50 OD 1 00 SYS 6 1 25 OD 1 00 SYS 7 1 00 OD 1 00 SYS 8 1 00 OD 1 25 SYS 9 1 00 OD 1 50 SYS 10 1 00 OD 2 00 SYS 11 1 00 OD 3 00 SYS 12 1 00 OD 4 00 SYS...

Страница 41: ...eeded as well as preserve the battery life seQ and MoV reset ratIo settIngs Each of the boiler loop SEQ and motorized valve loop MOV has their own reset ratio settings that can be configured independe...

Страница 42: ...Point temperature was 130 F and the Offset was changed from 0 to 10 an increase of 10 then the Set Point temperature would increase to 140 F TARGET OFFSET 0 F BACK SAVE The Offset setting does not ch...

Страница 43: ...ar on the main display indicating this condition Setback to 160 F For example if the calculated temperature is 180 F and the Setback is 20 F then when in Setback the SQ Elite MV will hold a Set Point...

Страница 44: ...4 20mA EMS Interface optional Reset Ratio Range Outdoor Reset Only 1 4 to 8 1 Outdoor System Water and Custom Reset Ratio Offset Adjustment Outdoor Reset Only minus 40 F 22 C to plus 40 F 22 C Minimum...

Отзывы: