SQ-Elite-MV & SQ-Elite-EXT Installation Manual
5
understandIng operatIon concept
The SQ-Elite-MV has multiple operating modes that satisfy most hydronic systems. It can
change any the of the loop temperatures' set point based on outdoor temperature. Or, it can
sequence stages to achieve an adjustable fixed Set Point.
In Outdoor Reset, it controls a hot water heating system to provide a building with comfortable
and even heat levels. The SQ-Elite-MV varies the temperature of the circulating heating
water in response to changes in the outdoor temperature. The SEQ heating water temperature
is controlled through the sequencing of the stages. The MOV heating water is controlled by
modulating the motorized valve.
The SQ-Elite-MV also controls both boiler loop and motorized valve loop circulating pumps
each with their own adjustable Outdoor Cutoff. When the outdoor temperature is above the
Outdoor Cutoff, the system pump is turned off and no heating water is circulated through that
loop. When the outdoor temperature drops below the Outdoor Cutoff, the system pump relay is
activated and the heating water circulates through the system. The temperature of the heating
water is controlled by the Reset Ratio, Water Offset, and changes to Outdoor temperature.
reset ratIo/outdoor reset
When a building is being heated, heat escapes through the walls, doors, and windows to
the colder outside air. The colder the outside temperature, the more heat escapes. If you
can input heat into the building at the same rate that it is lost out of the building, then the
building temperatures will remain constant. The Reset Ratio is an adjustment that lets
you achieve this equilibrium between heat input and heat loss.
The starting point for most systems is the 1.00 (OD):1.00 (SYS) (Outdoor Temperature
: Heating Water Temperature) ratio. This means that for every degree the outdoor
temperature drops, the temperature of the heating water will increase one degree. The
starting point of the curves is adjustable, but comes factory selected at 70
°
F Outdoor
Temp. and 100
°
F Water Temp. For example with a 1.00 (OD):1.00 (SYS) ratio, if the
outdoor temperature is 50
°
F, this means the temperature has fallen 20
°
from the starting
point of 70
°
F. Therefore, the heating water temperature will increase 20
°
to 120
°
F.
Each building has different heat loss characteristics. A very well insulated building will
not lose much heat to the outside air, and may need a Reset Ratio of 2.00 (OD):1.00
(SYS) (Outdoor:Water). This means the outdoor temperature would have to drop 2
degrees to increase the water temperature 1 degree. On the other hand, a poorly insulated
building with insufficient radiation may need a Reset Ratio of 1.00 (OD):2.00 (SYS).
This means that for each degree the outdoor temperature dropped the water temperature
will increase 2 degrees. The SQ-Elite-MV has a full range of Reset Ratios to match any
buildings heat loss characteristics.
A heating curve that relies not only on Outdoor temperature but also on type of radiation
will improve heat comfort. The following are suggested initial settings for different types
of radiation based on average building insulation and heat loss. The contractor can fine
tune these adjustments based on the specific building need.
type of radiation in Building
reset ratio
offset
Radiators (Steel & Cast Iron)
1.00 (OD) : 1.00 (SYS)
0˚F
Baseboard (Finned copper tube& Cast Iron)
1.00 (OD) : 1.00 (SYS)
0˚F
Radiant (High Mass/Concrete)
4.00 (OD) : 1.00 (SYS)
-10˚F
Radiant (Low Mass/Joists)
2.00 (OD) : 1.00 (SYS)
-10˚F
Fan Coils & Air Handlers
1.00 (OD) : 1.00 (SYS)
20˚F
Outdoor Temperature
W
a
te
r
T
e
m
p
e
ra
tu
re
70
40
50
60
130
120
110
100
Outdoor Temperature
W
a
te
r
T
e
m
p
e
ra
tu
re
70
40
50
60
110
100
90
80
Outdoor Temperature
W
a
te
r
T
e
m
p
e
ra
tu
re
70
40
50
60
150
140
130
120
1:4
With a 0° Offset, the
ratio curves begin at
100° Water Temperature.
With a -20° Offset, the
ratio curves begin at
80° Water Temperature.
With a +20° Offset, the
ratio curves begin at
120° Water Temperature.
1:4
1:4
1:1
1:1
1:1
4:1
4:1
4:1
90
100
+20 Offset
-20 Offset
(O) Outdoor Temperature (in °F)
70
60
50
40
20
30
0
-10
10
-20
100
120
110
130
140
150
160
180
170
190
200
210
220
1:3
1:2
1:1.5
1:1.25
1:1
1.25:1
1.5:1
2:1
3:1
4:1
(S) W
ater
T
emperature (in °F)
Reset Ratio Curves
Reset Ratio is Presented as
Outdoor Temp.(O) : Water Temp.(S) Ratio
1:4
8:1
warnIng
when controlling a non condensing
boiler, the seQ minimum boiler water
temperature must be set to boiler
manufacturer specifications. In that
case, seQ system temperature must
not go below such temperature.