16
Heat-Timer Corp.
----- BOILER AB -----
Mode
Auto
Runtime
58Hrs
<Prev Boiler>
<Next Boiler>
BACK SAVE
-- BOILER AB MODE
-
Auto
Standby
Off
On
BACK SAVE
BOILER AB RUNTIME
58hrs
BACK CLEAR OK
------ SETTINGS ------
Season
Winter
<SEQ Settings>
<MOV Settings>
<Maintenance>
<System Startup>
BACK SELECT
SEQ=
138
F
MOV=
128
F
OD=40 F RTN=122 F
SEQ TGT=140 F
MOV TGT=130 F
<AB>
CD
EF
HI
LO
--
--- SEQ SETTINGS ---
Set Point
140 F
EMS Set Pnt 140 F
<Outdoor Rst>
140 F
Min Return
<System Settings>
BACK SELECT
SEQ SYSTEM SETTING
<Stage Settings>
<Setback Schedule>
DHW Prior Timer No
Run-On
2m
Pump Exercise Off
BACK SELECT
- STAGE SETTINGS --
Reaction Time 1min
Purge Delay 0.0min
Min Runtime 2min
Standby Delay
10min
Last Stge Hold 5 F
Throttle
2 F
<Lead Settings>
BACK SELECT
-- REACTION TIME --
2min
[
]
BACK SAVE
--- PURGE DELAY ----
0.0min
[ ]
BACK SAVE
- MINIMUM RUNTIME -
2min
[
]
BACK SAVE
-- STANDBY DELAY --
10min
[
]
BACK SAVE
LAST STAGE HOLD
5 F
[
]
BACK SAVE
-- LEAD SETTINGS --
Lead Boiler
AB
Rotate Mode Time
BACK SELECT
-- LEAD BOILER --
AB
CD
BACK SELECT
-- LEAD ROTATION --
Time
Manual
FOFO
BACK SELECT
AUTO ROTATE PERIOD
24hrs
[ ]
BACK SAVE
-- THROTTLE RANGE --
2 F
[
]
BACK SAVE
lead / rotatIon
seQ stage settIngs
seQ stage
seQuencIng Menu
and stage Menu