SQ-Elite-MV & SQ-Elite-EXT Installation Manual
15
------ SETTINGS ------
Season
Winter
<SEQ Settings>
<MOV Settings>
<Maintenance>
<System Startup>
BACK SELECT
SEQ=
138
F
MOV=
128
F
OD=40 F RTN=122 F
SEQ TGT=140 F
MOV TGT=130 F
<AB>
CD
EF
HI
LO
--
--- SEQ SETTINGS ---
Set Point
140 F
EMS Set Pnt 140 F
<Outdoor Rst>
140 F
Min Return
<System Settings>
BACK SELECT
---- SET POINT ----
140 F
[
]
BACK SAVE
-- OUTDOOR CUTOFF -
70 F
[
]
BACK SAVE
---- RESET RATIO ---
Custom
1(8.00 OD:1.00 SYS)
2(4.00 OD:1.00 SYS)
3(3.00 OD:1.00 SYS)
4(2.00 OD:1.00 SYS)
5(1.50 OD:1.00 SYS)
6(1.25 OD:1.00 SYS)
7(1.00 OD:1.00 SYS)
8(1.00 OD:1.25 SYS)
9(1.00 OD:1.50 SYS)
10(1.00 OD:2.00 SYS)
11(1.00 OD:3.00 SYS)
12(1.00 OD:4.00 SYS)
BACK SAVE
SEQ OUTDOOR RESET
Reset Ratio
7
Target 0 F
Outdoor Cutoff
70 F
Min Target
80 F
Max Target
240 F
BACK SELECT
-- TARGET OFFSET ---
+0 F
[
]
BACK SAVE
---- MIN TARGET ----
80 F
[
]
BACK SAVE
---- MAX TARGET ----
240 F
[
]
BACK SAVE
---- MIN RETURN ----
120 F
[
]
BACK SAVE
seQ Menu
seQ reset settIngs
page
--- PUMP EXERCISE --
Off
On
BACK SAVE
------- RUN-ON -------
2min
[
]
BACK SAVE
DHW PRIORITY TIMER
30min
[ ]
BACK SAVE
SEQ SYSTEM SETTING
<Stage Settings>
<Setback Schedule>
DHW Prior Timer No
Run-On
2m
Pump Exercise Off
BACK SELECT
seQ stage settIngs
.
seQ systeM settIngs
page
------ SETBACK -------
0 F
[ ]
BACK SAVE
- NIGHT SCHEDULE --
07:**Pm
BACK SAVE
-------- BOOST ---------
0 F
[ ]
BACK SAVE
seQ setBack scHedules
SETBACK SCHEDULE
Setback
0 F
Present Time **:**
Day Schdul 7:00Am
Night Schdul
7:00Pm
BACK SELECT
-- DAY SCHEDULE ----
07:**Am
BACK SAVE
----- BOOST PERIOD---
30min
[
]
BACK SAVE