Heat & Glo • CERONA-36-IFT, CERONA-42-IFT Installation Manual • 2558-980 Rev. C • 3/21
40
10
10
Finishing
Risk of Fire!
DO NOT
apply combustible materials beyond the min-
imum clearances. Comply with all minimum clearanc-
es to combustibles as specified in this manual.
Ma-
terials overlapping into non-combustible zones could
ignite and will interfere with air flow through decora
-
tive barrier fronts.
• Metal front of appliance may be covered with non-
combustible materials only.
• Facing and/or finishing materials must not interfere
with air flow through decorative barrier fronts, removal
of decorative barrier fronts or access for service.
• Facing and/or finishing materials must never
overhang into the glass opening.
• Observe all clearances when applying combustible
materials.
• Seal gaps between the finished wall and appliance
top and sides using a 300 ºF minimum sealant. Refer
to Figure 10.1.
WARNING
A. Facing Material
Risk of Fire
• Non-combustible clearances
MUST
be
maintained.
• Sheetrock, wood or other combustibles must
NOT
be used as sheathing or facing in the
non-combustible zone.
• See
Section 3
for proper clearances.
• See
Section 1
for combustible/non-
combustible definitions.
WARNING
Figure 10.1
A
B
C
CERONA-36-IFT
in.
49
16-3/4 43-5/8
mm
1245
425
1108
CERONA-42-IFT
in.
45-1/4 16-3/4 50-5/8
mm
1149
425
1286
A
B
1 in.
(25)
C
CEILING
COMBUSTIBLE
SHEATHING
NON-COMBUSTIBLE
FACING MATERIAL
IN SHADED AREAS
APPLIANCE
ARCH OPENING
CLEARANCE
TO CEILING
MINIMUM
BOTTOM OF APPLIANCE
TO BOTTOM OF
NON-COMBUSTIBLE
FACING MATERIAL