Heat & Glo • REVO-V12, REVO-S21, REVO-H31 Installation Manual • 2273-980 Rev. J • 5/15
60
MANTEL LEG OR
PERPENDICULAR WALL
12 IN.
IN-WALL TUB MOUNT
TOP VIEW
VERTICAL FRAMING STUDS
1/2 IN.
SHEETROCK/COMBUSTIBLE
FACING MATERIAL
FROM
IN-WALL
TUB
OPENING
1-1/2 IN. FROM
SHEETROCK/COMBUSTIBLE
FACING MATERIAL
0 IN.
FROM
IN-WALL
TUB OPENING
1/2 IN.
MAX.
UNLIMITED
APPLIANCE
OUTER WRAP
TUB
Figure 11.11 Combustible Mantel Leg or Wall Projections
(Acceptable on both sides of opening)
Combustible Mantel Legs or Wall Projections
Figure 11.12 Non-Combustible Mantel Leg or Wall Projections
(Acceptable on both sides of opening)
Non-Combustible Mantel Legs or Wall Projections
= 0 IN. MIN.
FROM IN-WALL TUB OPENING
MANTEL LEG OR
PERPENDICULAR WALL
IN-WALL TUB MOUNT
TOP VIEW
APPLIANCE
OUTER WRAP
VERTICAL FRAMING STUDS
1-1/2 IN. FROM
SHEETROCK/COMBUSTIBLE
FACING MATERIAL
= 6 IN. MIN.
FROM IN-WALL
TUB OPENING
UNLIMITED
TUB
SHEETROCK/COMBUSTIBLE
FACING MATERIAL
1/2 IN. MAX.
Figure 11.13 Minimum Vertical and Maximum Horizontal
Dimensions of Combustibles
Note:
All
measurements
in inches.
MEASUREMENTS FROM TOP
OF APPLIANCE OUTER WRAP
15 IN. MIN.
18 IN. MIN.
22 IN. MIN
TO CEILING
APPLIANCE OUTER WRAP
6 IN. MAX.
3 IN. MAX.
SHEETROCK 1/2 IN. MAX. THICKNESS
IN-WALL TUB AND APPLIANCE
BEHIND SHEETROCK/COMBUSTIBLE FACING MATERIAL
Combustible Mantels Above Appliance Outer wrap
D. In-Wall Mantel and Wall Projections
Figure 11.14 Minimum Vertical and Maximum Horizontal
Dimensions of Non-Combustibles
Non-Combustible Mantels Above Appliance
Outer wrap
MEASUREMENTS FROM TOP
OF APPLIANCE OUTER WRAP
1-1/2
IN.
1/2 IN. MIN. OR FLUSH WITH
IN-WALL TUB OPENING
6 IN. MIN.
9 IN. MIN.
12 IN. MIN.
22 IN. MIN.
TO CEILING
APPLIANCE OUTER WRAP
3 IN.
MAX.
6 IN. MAX.
9 IN. MAX.
SHEETROCK 1/2 IN. MAX. THICKNESS
IN-WALL TUB
AND APPLIANCE
BEHIND SHEETROCK/
COMBUSTIBLE
FACING MATERIAL
1/2 IN. MAX.