023-00354-Rev1.4 evc/epc
User
Manual
Copyright © High Country Tek, Inc. – 2013
29
evc/epc
Controller
With
SAE
J1939
Interface
Fixed
Set-point
RPM
RPM
Stop
1500rpm
RPM
Slow
1800rpm
Coil
A
0
Current
When “Auto-Reverse” is “
OFF
”, Coil A current stays 0 until the RPM increases to above “RPM Stop”, it
will increase proportionally to the measured RPM.
When “Auto-Reverse” is “
ON
”, Coil A current stays at 0 and Coil B current will ramp up to the Reverse
Set-point.
After the reverse cycle is over, if the measured RPM increases to above RPM Stop, Coil A current
increases proportionally. If not, the evc/epc will try Reverse Retry Count times, each time remaining in
reverse for reverse time.
If the Reverse Retry Count is depleted and the measured RPM remains below RPM Stop, the evc/epc
will declare an error.
At start-up the measured RPM must initially reach the “RPM Slow” to allow the evc/epc to ramp up Coil
A. This ensures that the prime mover has started and is at a stable speed
.
Coil
B
RPM
Slow
(1800rpm)
Reverse
Set-point
RPM
Stop
(1500rpm)
Fixed
Set-point
Coil
A