023-00354-Rev1.4 evc/epc
User
Manual
Copyright © High Country Tek, Inc. – 2013
17
evc/epc
Controller
With
SAE
J1939
Interface
Coil A/B Max
Current
(0 to 3Amps)
When Current Feedback is “
ON
”, it determines the max current.
When Current Feedback is “
OFF
”, the Coil A/B Min Current setting does not apply and is grayed out. The
Max Current is used as a reference for the evc/epc to declare a coil short condition
when the output
current is
0.5A higher
than the max setting.
The output PWM duty cycle
matches the percent of demand.
The current will change when
supply voltage and/or coil
temperature changes.
The evc/epc does not declare an
error because the output current
1.16A is
not
0.5A higher
than the
max setting 0.7A.
The evc/epc will declare an error
because the output current 1.16A is
0.5A higher
than the max setting
0.63A.
Ramp Up
(.001 to 65.000 Seconds) – Determines the time for Output A or B to ramp
UP
from minimum to
maximum current.
Ramp Down
(.001 to 65.000Seconds) – Determines the time for Output A or B to ramp
Down
from
maximum to minimum current.
Coil A&B PWM Hz
(33 to 500Hz) – This is the PWM or Dither frequency according to the valve spec.
(Sun cartridges are 140Hz).