023-00354-Rev1.4 evc/epc
User
Manual
Copyright © High Country Tek, Inc. – 2013
21
evc/epc
Controller
With
SAE
J1939
Interface
Command Input Selection
0-5V
dc
0-10V
dc
4-20mA
Inverted
– When set, will reverse the response of the
command input. The min input voltage demands 100% output
and the max input voltage demands 0% output.
For industrial applications, the input is ±5V
dc
or ±10V
dc
, please use a Command Signal Conditioner with
the evc/epc controller.
CSC-0505 – accepts ±5V
dc
and converts to 0-5V.
CSC-1005 – accepts ±10V
dc
and converts to 0-5V.
Loss of Pulse Signal Time
– (1 mS to 65 Sec) Sets the time
delay before a loss of pulse signal causes an error to be
declared.
Coil A or B default set-point
– (0-100%)
When Set, Output A
or B will ramp to this value when the limits are exceeded.
Command Limit Settings
Pot Deadband
The Pot Deadband can only be used when the Analog Center Active is “
ON
”.
Deadband is split one half above, one half below the center point.
0.2V
dc
means coil A starts to have output at 2.6V
dc
, coil B starts to have output at 2.4V
dc
.