Pulse Input Settings
Pulse Input Selections
(Analog or Pulse) – Selects
the pulse input or analog input.
0 to 5V, 0 to 10V & ±1V
(Enabled/Off) – Match the
voltage range to the PPU or analog spec.
±1V
only
applies to Pulse input.
Pulses per revolution
PPR
- (1 to 65535) – Scales the actual RPM from the measured pulse period.
Maximum displayed RPM
(1 to 65535) – It scales the RPM gauge on the Dashboard.
Keep this value near the maximum RPM to assure the best resolution and accuracy.
RPM slow Set-Point or Max Load RPM
(1 to 65535) – The set-point where coil A current starts to
reduce in Anti-Stall or HP limit modes.
RPM stop
Set-Point or No Load RPM
(1 to 65535) – The set-point where coil A current reaches 0 in
Anti-Stall or HP limit modes. If auto-reverse is ON, reverse cycle will start at this rpm.