6.1.5.2 sC-3000/sC-4000 Dual Fuel 480 Volt

Содержание P-K SONIC SC-3000

Страница 1: ...ee 877 728 5351 Fax 570 476 7247 www harscopk com 2013 Harsco Industrial Patterson Kelley SONIC201 Revised June 12 2014 C S A Design Certified Complies with ANSI Z21 13 CSA 4 9 Gas Fired Low Pressure...

Страница 2: ...al connections for tightness as connections may come lose during shipping Venting Maintain exhaust pressure from 04 wc to 22 wc Hydronics Maximum Flow SC 4000 384 gpm SC 3000 285 gpm Minimum Flow Igni...

Страница 3: ...itches 23 3 10 Initial Adjustments 23 3 10 1 Operating Temperature Controller 23 3 10 2 Boiler Set Point 24 3 10 3 Other CH Parameters 24 3 10 4 Other Parameters 24 3 10 5 Additional Menu Items 24 3 1...

Страница 4: ...s fired boilers are fully modulating using variable speed combustion blowers sophisticated microprocessor controls modulating gas safety shut off control valves and a unique stainless steel heat excha...

Страница 5: ...res de verrouillage signalisation lors de l entretien WARNING Improper use may result in fire or injury Read instructions safety manual before installing operating or servicing boiler The safety label...

Страница 6: ...ainer and be covered by a tarpaulin or other waterproof covering 3 1 1 Initial Inspection Upon receiving the boiler inspect it for signs of shipping damage Some damage may be hidden Unpack the boiler...

Страница 7: ...connected to the DHW temperature sensor or thermostat This circuit is energized by the boiler with a 5V potential The temperature sensor must be a NTC having 12k 77 F Header Temp Sensor TB1 9 and TB1...

Страница 8: ...re that may cause excessive condensate production in the vent Direct Vent An appliance that is constructed and installed so that all air for combustion is derived directly from outdoors and all flue g...

Страница 9: ...d by deducting the blockage area of any fixed louvers grilles or screens from the total area of the opening 2 Screens shall be not smaller than 3 Motorized louvers shall be interlocked with the applia...

Страница 10: ...echnical Service 1 877 728 5351 INSTALLATION Gas Fired Boiler The boiler vent should not be connected into any portion of another mechanical draft system without consulting the vent manufacturer The b...

Страница 11: ...ll operate at maximum speed Do not operate a summer exhaust fan Close fireplace dampers 4 Place the appliance being inspected in operation Follow the lighting instructions Adjust the thermostat so tha...

Страница 12: ...tted to the boiler The boiler shall not be used as a pipe anchor When installed in a two pipe system that provides both chilled and hot water the control system should be configured so as to limit the...

Страница 13: ...guration 2 Place the boiler in operation at the high fire setting BNR TEST MODE HI 3 Smoothly close the downstream manual isolation valve to reduce the gas flow and cause flame failure 4 The display w...

Страница 14: ...hnician to hold the boiler in high or low fire during firing operation so that the combustion adjustment can be performed as indicated below The second test mode checks the fan rate with the burner of...

Страница 15: ...ssary 3 11 3 Checking Flame Signal Using the control panel enter the information mode and scroll down view the flame signal This shows A when the boiler is firing and shows 0 A when the boiler is not...

Страница 16: ...orrective action or repair 5 1 2 Weekly Observe the conditions of the main flame A normal high fire flame is mostly orange with a blue halo while at low fire the burner will glow yellowish orange Corr...

Страница 17: ...temperature low water level WARNING 5 6 Troubleshooting 5 6 3 Low Gas Pressure The low gas pressure switch opens when there is or has been insufficient gas pressure available for proper operation of...

Страница 18: ...INTERNAL ERROR 31 Internal Error 31 Call for service Code ENVI Display Lockout Description E01 OUT TEMP SENS OPEN Outlet Temperature Sensor Open Boiler outlet water temperature sensor open circuit E02...

Страница 19: ...o not ground through the conduit Terminal Number Label Description 3 120V AC Neutral Neutral for use with TB2 10 Switched Output 4 120V AC Neutral Neutral for use with TB2 11 3 Way Valve 5 120V AC Neu...

Страница 20: ...ly configured for either 208V 220 240V or 440 480V three phase 60 hertz service Improper configuration of the transformer could result in serious injury or death The high voltage TB2 terminal block is...

Страница 21: ...77 728 5351 Gas Fired Boiler 38 Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 Gas Fired Boiler PARTS TECHNICAL SUPPORT PARTS TECHNICAL SUPPORT SC 3000 SC 4000 220 240 VAC three p...

Страница 22: ...1 877 728 5351 Gas Fired Boiler 40 Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 Gas Fired Boiler PARTS TECHNICAL SUPPORT PARTS TECHNICAL SUPPORT 6 1 5 SC 3000 SC 4000 Boiler Wir...

Страница 23: ...lley Technical Service 1 877 728 5351 Gas Fired Boiler 42 Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 Gas Fired Boiler PARTS TECHNICAL SUPPORT PARTS TECHNICAL SUPPORT 6 1 5 2 S...

Страница 24: ...on Kelley Technical Service 1 877 728 5351 Gas Fired Boiler 44 Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 Gas Fired Boiler PARTS TECHNICAL SUPPORT PARTS TECHNICAL SUPPORT 6 1...

Страница 25: ...on Kelley Technical Service 1 877 728 5351 Gas Fired Boiler 46 Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 Gas Fired Boiler PARTS TECHNICAL SUPPORT PARTS TECHNICAL SUPPORT 6 1...

Страница 26: ...5 7 6 4 B 2 4 A Mark Description 1 Heat Exchanger 2 Blower Burner Assembly 3 Base 4 A Gas train LP 4 B Gas Train Natural Gas 5 Controller 6 Electrical Box 7 Front Door Control Panel 8 Cabinet 6 2 1 Ma...

Страница 27: ...Water Connection 5 Condensate Collector 6 Igniter 7 Burner 8 Burner Gasket 9 Burner Hood 6 2 3 SC 3000 SC 4000 Heat Engine Mark Description 1 Burner 2 Burner Transition Piece 3 Blower 4 Venturi 5 Manu...

Страница 28: ...cial or consequential damages such as loss of the use of products facilities or production inconvenience loss of time or labor expense involved in repairing or replacing the alleged defective Product...

Страница 29: ...Date Hi Low Fire O2 CO CO2 Stack Temp pH Action By Appendix 1 Maintenance Log 54 Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 APPENDIX 1 Gas Fired Boiler...

Страница 30: ...in section 3 10 4 to get 5 O2 in the flue gas If this cannot be achieved perform the following steps If the O2 is too high then the inlet gas pressure should be adjusted to the minimum pressure allow...

Страница 31: ...ntire hydronic system Samples of the system water with cleaner should be taken and analyzed to ensure proper cleaner strength Once cleaned the system should be flushed with fresh fill water until the...