background image

22

Harsco Industrial, Patterson-Kelley Technical Service 1.877.728.5351

INST

alla

TION

Gas Fired Boiler

The 

SC-3000

 and 

SC-4000

 boilers are 

equipped with 

ENVI®

 

control; an intelligent 

control system 

with advanced 

features such as 

text-based display, 

communication 

capabilities, and 

boiler sequencing. 

Errors are date 

and time stamped 

providing built-in

 

history of boiler 

status and performance.
This control constantly tracks the load by recording burner high, low and mid run hours. One control to do it 

all – temperature control, flame safeguard, firing rate control, blocked flue protection, outdoor air reset, freeze 

protection, built-in cascade sequencing, MODBUS communication and more. 
The boiler control has a text display panel. The display panel is used to setup and monitor boiler operation by 

means of six push buttons 

MENU

BACK

ENTER

UP

DOWN

, and 

RESET

 as shown above. The buttons across 

the bottom are used to navigate through the various screens. The four line screen shows boiler operating 

information on various screens. The display screen is back lit for ease of viewing. Pressing any key will illuminate 

the back light.

*NOTE 1 - Refer to ENVI® Control Advanced Users Guide (Part # 1004905953) for more information.

23

Harsco Industrial, Patterson-Kelley Technical Service 1.877.728.5351

INST

alla

TION

Gas Fired Boiler

After checking controls by manual 

adjustment, make sure they are 

always reset to their proper settings. 

Never attempt to operate a boiler 

that has failed to pass all the safety 

checks described below. 

Before attempting to start the boiler, make sure the following items have 

been completed. Refer to the engineering manual for your model for 

additional information.

1. Inspect the gas train, blower, ignition electrode and boiler in general to be sure 

there was no damage during shipment or installation.
2. Flue gas from the boiler is properly vented;
3. Gas connection has been made, pressure tested for leakage and the line 

purged of air. Make sure all required vents have been installed.
4. Water connections are complete and the boiler and system have been filled 

and purged of air.
5. The boiler is connected to the correct electrical power source listed on the 

nameplate, and having a disconnect having adequate overload protection.
6. Combustion air openings are not obstructed in any way and have adequate   

                                                                      capacity.
7. The boiler is placed the proper distance from any combustible walls
8. Relief valves have been piped to an acceptable drain at a safe point of discharge.
9. Condensate piping is properly connected.
10. Verify system water quality is within specifications. 

3.8 p

re

-s

TarT

 C

heCklIsT

The following checks of safety systems must be made before putting the boiler into normal operation.
Before firing the boiler refer to 

Section 4

 for information on the use of the controls, lighting, and shut-down 

procedures. 

3.9 s

afeTy

 C

heCks

!

WARNING

If the expected error code(s) do not 

appear, call for qualified service.

n

oTICe

!

Test the ignition system safety shutdown as follows:

1. Cycle the boiler on by generating a heat request. (The method for this will depend on your boiler configuration.)
2. Place the boiler in operation at the high fire setting BNR TEST MODE HI.
3. Smoothly close the downstream manual isolation valve to reduce the gas flow and cause flame failure.
4 The display will show LOCKING FLAME FAILURE indicating a flame failure. The lockout will remain until the control is reset.

After completing this test, turn off the boiler and open the downstream manual isolation valve and turn the boiler 

back on.

3.9.1 test of Ignition safety system

The boiler is furnished with a probe-type low water cut-out in the outlet nozzle. Test as follows:
Push and hold the red “Push to test” button for at least 5 seconds. A manual lockout reset error displaying 

LOCKOUT LOW WATER LEVEL

 on the display panel should occur. The 

LED

 indicator on the Low Water cut-off will no 

longer be illuminated.

Optional Test Method: 

First turn the boiler off, and then turn the pump off. Isolate the boiler from the system.Drain 

the water level below the low water cut-off probe. Turn the boiler back on. It should not operate, and a manual 

lockout reset error displaying 

LOCKOUT LOW WATER LEVEL

 on the display panel should occur. The 

LED

 indicator 

on the Low Water cut-off will no longer be illuminated.
Return the system to normal operation by refilling and restarting the boiler and pump.

3.9.2 test of low Water Cut-out

3.9.3 test of high-limit Control

Fire the boiler and test the high limit control as follows:
With the main burner operating, turn down the temperature setting on the "high-limit" thermostat until the main 

burner shuts off. A manual reset lockout displaying 

LOCKING HIGH LIMIT 

on the display panel will occur. The 

high-limit switch must be manually reset prior to resetting the boiler at the display panel. Readjust the high-limit 

thermostat to the desired setpoint.

low Gas Pressure switch

The boiler is furnished with a low gas pressure switch. The operation of this switch must be checked by slowly 

closing the main gas cock while the burner is operating. The switch should shut down the main burner. When 

the gas pressure switch opens, a manual reset lockout displaying 

LOCKING LOW GAS PRESSURE

 on the display 

panel will occur. Upon re-opening the main gas cock, the

 LOCKING LOW GAS PRESSURE

 will remain on until the 

display panel is manually reset.

high Gas Pressure switch

The boiler is furnished with a high pressure switch that must be checked by closing the downstream gas cock 

with the boiler off. When the boiler is started, it should enter its normal starting cycle and fail on high gas pressure 

when the automatic gas valves open. The high gas pressure switch actuation is evident when a manual reset 

lockout displaying

 LOCKING HIGH GAS PRESSURE

 on the display panel occurs. Upon re-opening the gas cock, 

the

 LOCKING HIGH GAS PRESSURE

 indicator will remain on until the display panel is manually reset.

3.9.4 test of Gas Pressure switches 

The user should become 

thoroughly familiar with the 

operation of the boiler and controls 

before attempting to make any 

adjustments.

!

CAUTION

Changing parameters requires an 

understanding of the parameters 

and the functionality of the boiler.

The boiler may not function 

properly if parameters are changed 

from the factory values. 

!

CAUTION

3.10 I

nITIal

 a

djusTMenTs

3.10.1 Operating temperature Controller

!

WARNING

Figure 3.10.1a

Содержание P-K SONIC SC-3000

Страница 1: ...ee 877 728 5351 Fax 570 476 7247 www harscopk com 2013 Harsco Industrial Patterson Kelley SONIC201 Revised June 12 2014 C S A Design Certified Complies with ANSI Z21 13 CSA 4 9 Gas Fired Low Pressure...

Страница 2: ...al connections for tightness as connections may come lose during shipping Venting Maintain exhaust pressure from 04 wc to 22 wc Hydronics Maximum Flow SC 4000 384 gpm SC 3000 285 gpm Minimum Flow Igni...

Страница 3: ...itches 23 3 10 Initial Adjustments 23 3 10 1 Operating Temperature Controller 23 3 10 2 Boiler Set Point 24 3 10 3 Other CH Parameters 24 3 10 4 Other Parameters 24 3 10 5 Additional Menu Items 24 3 1...

Страница 4: ...s fired boilers are fully modulating using variable speed combustion blowers sophisticated microprocessor controls modulating gas safety shut off control valves and a unique stainless steel heat excha...

Страница 5: ...res de verrouillage signalisation lors de l entretien WARNING Improper use may result in fire or injury Read instructions safety manual before installing operating or servicing boiler The safety label...

Страница 6: ...ainer and be covered by a tarpaulin or other waterproof covering 3 1 1 Initial Inspection Upon receiving the boiler inspect it for signs of shipping damage Some damage may be hidden Unpack the boiler...

Страница 7: ...connected to the DHW temperature sensor or thermostat This circuit is energized by the boiler with a 5V potential The temperature sensor must be a NTC having 12k 77 F Header Temp Sensor TB1 9 and TB1...

Страница 8: ...re that may cause excessive condensate production in the vent Direct Vent An appliance that is constructed and installed so that all air for combustion is derived directly from outdoors and all flue g...

Страница 9: ...d by deducting the blockage area of any fixed louvers grilles or screens from the total area of the opening 2 Screens shall be not smaller than 3 Motorized louvers shall be interlocked with the applia...

Страница 10: ...echnical Service 1 877 728 5351 INSTALLATION Gas Fired Boiler The boiler vent should not be connected into any portion of another mechanical draft system without consulting the vent manufacturer The b...

Страница 11: ...ll operate at maximum speed Do not operate a summer exhaust fan Close fireplace dampers 4 Place the appliance being inspected in operation Follow the lighting instructions Adjust the thermostat so tha...

Страница 12: ...tted to the boiler The boiler shall not be used as a pipe anchor When installed in a two pipe system that provides both chilled and hot water the control system should be configured so as to limit the...

Страница 13: ...guration 2 Place the boiler in operation at the high fire setting BNR TEST MODE HI 3 Smoothly close the downstream manual isolation valve to reduce the gas flow and cause flame failure 4 The display w...

Страница 14: ...hnician to hold the boiler in high or low fire during firing operation so that the combustion adjustment can be performed as indicated below The second test mode checks the fan rate with the burner of...

Страница 15: ...ssary 3 11 3 Checking Flame Signal Using the control panel enter the information mode and scroll down view the flame signal This shows A when the boiler is firing and shows 0 A when the boiler is not...

Страница 16: ...orrective action or repair 5 1 2 Weekly Observe the conditions of the main flame A normal high fire flame is mostly orange with a blue halo while at low fire the burner will glow yellowish orange Corr...

Страница 17: ...temperature low water level WARNING 5 6 Troubleshooting 5 6 3 Low Gas Pressure The low gas pressure switch opens when there is or has been insufficient gas pressure available for proper operation of...

Страница 18: ...INTERNAL ERROR 31 Internal Error 31 Call for service Code ENVI Display Lockout Description E01 OUT TEMP SENS OPEN Outlet Temperature Sensor Open Boiler outlet water temperature sensor open circuit E02...

Страница 19: ...o not ground through the conduit Terminal Number Label Description 3 120V AC Neutral Neutral for use with TB2 10 Switched Output 4 120V AC Neutral Neutral for use with TB2 11 3 Way Valve 5 120V AC Neu...

Страница 20: ...ly configured for either 208V 220 240V or 440 480V three phase 60 hertz service Improper configuration of the transformer could result in serious injury or death The high voltage TB2 terminal block is...

Страница 21: ...77 728 5351 Gas Fired Boiler 38 Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 Gas Fired Boiler PARTS TECHNICAL SUPPORT PARTS TECHNICAL SUPPORT SC 3000 SC 4000 220 240 VAC three p...

Страница 22: ...1 877 728 5351 Gas Fired Boiler 40 Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 Gas Fired Boiler PARTS TECHNICAL SUPPORT PARTS TECHNICAL SUPPORT 6 1 5 SC 3000 SC 4000 Boiler Wir...

Страница 23: ...lley Technical Service 1 877 728 5351 Gas Fired Boiler 42 Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 Gas Fired Boiler PARTS TECHNICAL SUPPORT PARTS TECHNICAL SUPPORT 6 1 5 2 S...

Страница 24: ...on Kelley Technical Service 1 877 728 5351 Gas Fired Boiler 44 Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 Gas Fired Boiler PARTS TECHNICAL SUPPORT PARTS TECHNICAL SUPPORT 6 1...

Страница 25: ...on Kelley Technical Service 1 877 728 5351 Gas Fired Boiler 46 Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 Gas Fired Boiler PARTS TECHNICAL SUPPORT PARTS TECHNICAL SUPPORT 6 1...

Страница 26: ...5 7 6 4 B 2 4 A Mark Description 1 Heat Exchanger 2 Blower Burner Assembly 3 Base 4 A Gas train LP 4 B Gas Train Natural Gas 5 Controller 6 Electrical Box 7 Front Door Control Panel 8 Cabinet 6 2 1 Ma...

Страница 27: ...Water Connection 5 Condensate Collector 6 Igniter 7 Burner 8 Burner Gasket 9 Burner Hood 6 2 3 SC 3000 SC 4000 Heat Engine Mark Description 1 Burner 2 Burner Transition Piece 3 Blower 4 Venturi 5 Manu...

Страница 28: ...cial or consequential damages such as loss of the use of products facilities or production inconvenience loss of time or labor expense involved in repairing or replacing the alleged defective Product...

Страница 29: ...Date Hi Low Fire O2 CO CO2 Stack Temp pH Action By Appendix 1 Maintenance Log 54 Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 APPENDIX 1 Gas Fired Boiler...

Страница 30: ...in section 3 10 4 to get 5 O2 in the flue gas If this cannot be achieved perform the following steps If the O2 is too high then the inlet gas pressure should be adjusted to the minimum pressure allow...

Страница 31: ...ntire hydronic system Samples of the system water with cleaner should be taken and analyzed to ensure proper cleaner strength Once cleaned the system should be flushed with fresh fill water until the...

Отзывы: