background image

14

Harsco Industrial, Patterson-Kelley Technical Service 1.877.728.5351

INST

alla

TION

Gas Fired Boiler

15

Harsco Industrial, Patterson-Kelley Technical Service 1.877.728.5351

INST

alla

TION

Gas Fired Boiler

under no circumstances shall 

the boiler room ever be under 

a negative pressure.

 Particular 

care should be taken when 

exhaust fans, compressors, air-

handling units or other equipment 

may rob air from the boiler. Note 

that this equipment might be 

in rooms other than the boiler 

room. This applies to both sealed 

combustion and atmospheric 

room combustion air applications.

!

WARNING

3.5.2.1 Air Inlet Requirements — united states (

NFPA 54/ANsI Z223.1 & NFPA/ANsI 211

)

When air is supplied from inside the building, the total required volume 

shall be the sum of the required volume for all the appliances located 

in the mechanical room. Adjacent rooms furnished with fixed openings 

communicating directly with the mechanical room are considered part of the 

required volume. The minimum volume is 50 ft

3

 per 1000 Btu/hr (4.8 m

3

/kW) of 

installed appliance input capacity.
Openings used to connect indoor spaces to obtain the required minimum 

volume shall be sized as follows:

• 

 When rooms are on the same floor, each opening shall have an area equal to 

1 square inch for each 1000 Btu/hr (2200 mm

2

/kW) of installed appliance input 

capacity, but not less than 100 square inches. One opening should commence 

less than 12 inches above the floor and the other less than 12 inches below the 

ceiling. The minimum dimension of air openings shall be 3 inches.

• 

 When rooms are on different floors, each opening shall have an area equal to 2 

square inches for each 1000 Btu/hr (4400 mm

2

/kW) of installed appliance input 

capacity.

When combustion air is supplied from outside the building, the boiler room 

shall be provided with one or two openings to ensure adequate combustion air 

and proper ventilation.
When using one permanent opening, the opening shall commence within 

12 inches of the ceiling and shall communicate directly with the outdoors or 

through a vertical or horizontal duct that communicates to the outdoors.  
Minimum free area of the opening is 1 square inch for each 3000 Btu/hr (700 

mm

2

/kW) of installed appliance input capacity, and not less than the sum of 

the areas of all vent connectors in the room.
When using two permanent openings, one opening shall commence within 

12 inches above the floor and the other within 12 inches below the ceiling, preferably on opposite walls. The openings 

shall communicate directly, or by way of ducts, with free outdoor air. The minimum net free area of the openings shall be 

calculated in accordance with the following:

• 

 When air is taken directly from outside the building, each opening (minimum of two, as outlined above), 1 square inch for 

each 4,000 Btu per hour (550 mm

2

/kW) of total boiler input is required.

• 

 When air is taken from the outdoors through a vertical duct into the mechanical room, 1 square inch per 4,000 Btu per hour 

(550 mm

2

/kW) of total boiler input is required.  

• 

 When air is taken from the outdoors through a horizontal duct into the mechanical room, 1 square inch per 2,000 Btu per 

hour (1100 mm

2

/kW) of total boiler input is required.

n

oTe

:

 

1. The required size of openings for 

combustion and ventilation air shall 

be based on the net free area of the 

opening.

2. Screens shall be not smaller than ¼”
3. Motorized louvers shall be 

interlocked with the appliance so that 

they are proven open prior to main 

burner ignition and operation.

3.5.2.2 Air Inlet Requirements – Canada (CAN/CsA B149.1)

A. Ventilation of the space occupied by fuel burning appliance(s) or equipment shall be supplied by a ventilation 

opening at the highest practicable point communicating with the outdoors. The total cross sectional area of the 

ventilation opening must be either 10% of the net free area required for combustion air or 10 sq. in. (6500 mm

2

), 

whichever is greater.

n

oTe

:

1. The free area of a combustion 

air supply opening is calculated by 

deducting the blockage area of any 

fixed louvers, grilles or screens from 

the total area of the opening.
2. Screens shall be not smaller than ¼”
3. Motorized louvers shall be 

interlocked with the appliance so that 

they are proven open prior to main 

burner ignition and operation.

P-K sONIC™ 

Boiler model

AIR sOuRCe

INDOOR AIR suPPly

OutDOOR AIR suPPly

sAme FlOOR DIFF FlOORs ONe OPeNING

tWO OPeNINGs

DIReCt  

VeRt DuCt

hORIZ DuCt

SC-3000

3000

6000

1000

750

750

1500

SC-4000

4000

8000

1334

1000

1000

2000

US Minimum area of ventilation openings per boiler (sq inches)

B. Use the following opening calculation for P-K SONIC™, MACH® or 

MODU-FIRE® FD

 boilers:

When combustion air is supplied for a forced draft burner by natural airflow from 

the outdoors and there is no draft regulator or draft hood in the same space, there 

shall be a permanent opening with a cross sectional area not less than 1 sq. in/ 

30,000 Btu/Hr (70 mm

2

/kW) of the total rated input to the burner(s). This opening 

must not interfere with the ventilation air opening defined in paragraph A.

C. Use the following opening calculation for 

P-K THERMIFIC®

 boilers or 

other natural draft or fan-assist appliances:

When combustion air is supplied for natural or fan-assisted burners by natural 

airflow from the outdoors, there shall be a permanent opening with a cross 

sectional area not less than 1 sq. in/7000 Btu/Hr (321 mm

2

/kW) up to and 

including 1,000,000 Btu/Hr plus 1 sq. in./14,000 Btu/Hr (155 mm

2

/kW) in excess 

1,000,000 Btu/Hr. This opening must be either located at or ducted to a point not more than 18 in. (450 mm) or less than 6 in. 

(150 mm) above floor level. This opening is in addition to the ventilation air opening defined in paragraph A.

D. When combustion air is supplied by natural airflow into a space containing both types of appliance described 

in paragraphs B and C, the cross sectional area of the opening shall be not less than the sum of the cross 

sectional areas for all appliances in the space as calculated by the applicable method. This opening is in addition 

to the ventilation air opening defined in paragraph A.
E. When a duct is used to meet the requirement for combustion air supply, as described in paragraphs A through 

D, above, the opening of the duct shall be located so there is no possibility of cold air affecting steam or water 

piping, electrical equipment or mechanical equipment.
F. When combustion air is supplied by mechanical means, an airflow-sensing device must be installed. It must be 

wired into the pre-ignition limit string to prevent the burner from starting or to stop an operating burner in case of 

air supply failure.  
G. When all combustion air is supplied through a make-up air heater, and the appliance is interlocked to the 

heater, the requirements of paragraphs A through F do not apply.

P-K sONIC™ Boiler

Required Combustion Air Opening

Ventilation Air Opening

model

Input (Btu/hr)

in

2

mm

2

in

2

mm

2

SC-3000

3,000,000

100

64,516

10

6,452

SC-4000

4,000,000

134

86,451

13.4

8,645

3.5.3 Flue Venting 

This boiler is not certified for use with Type "B" vent nor with 

PVC

 venting.  

P-K SONIC™

 boilers are dual certified as a Category II and Category IV appliances, as defined in 

ANSI Z21.13/CSA

 

4.9

, latest edition. The vent material must be as listed in the Table of Acceptable Materials for Venting Systems in 

Section 3.5.1.2 above. The exhaust vent can be run horizontally or vertically.
Vent installations shall be in accordance with 

NFPA54/ANSI Z223.1

, the National Fuel Gas Code, or 

CAN/

CSA-B149.1

, the Natural Gas and Propane Installation Code, or applicable provisions of the local building codes.

Canadian minimum Area of Combustion and Ventilation Air Openings

3.5.3.1 Vent sizing

The vent must be sized in accordance with the

 ASHRAE

 Systems and Equipment handbook, Chapter 30 or 

according to the vent manufacturer’s recommendations. When using manufactured venting systems, consult your 

vent supplier for correct sizing and structural support requirements.

P-K sONIC™ Boiler model

Frictional Resistance

stack temperature

CO2 Natural Gas

CO2 lP Gas

SC-3000/SC-4000

0.22” wc

220 °F

9.2%

10.4%

Vent Design Parameters

Table  3.5.2.1

Table 3.5.2.2

Table 3.5.3.1

Содержание P-K SONIC SC-3000

Страница 1: ...ee 877 728 5351 Fax 570 476 7247 www harscopk com 2013 Harsco Industrial Patterson Kelley SONIC201 Revised June 12 2014 C S A Design Certified Complies with ANSI Z21 13 CSA 4 9 Gas Fired Low Pressure...

Страница 2: ...al connections for tightness as connections may come lose during shipping Venting Maintain exhaust pressure from 04 wc to 22 wc Hydronics Maximum Flow SC 4000 384 gpm SC 3000 285 gpm Minimum Flow Igni...

Страница 3: ...itches 23 3 10 Initial Adjustments 23 3 10 1 Operating Temperature Controller 23 3 10 2 Boiler Set Point 24 3 10 3 Other CH Parameters 24 3 10 4 Other Parameters 24 3 10 5 Additional Menu Items 24 3 1...

Страница 4: ...s fired boilers are fully modulating using variable speed combustion blowers sophisticated microprocessor controls modulating gas safety shut off control valves and a unique stainless steel heat excha...

Страница 5: ...res de verrouillage signalisation lors de l entretien WARNING Improper use may result in fire or injury Read instructions safety manual before installing operating or servicing boiler The safety label...

Страница 6: ...ainer and be covered by a tarpaulin or other waterproof covering 3 1 1 Initial Inspection Upon receiving the boiler inspect it for signs of shipping damage Some damage may be hidden Unpack the boiler...

Страница 7: ...connected to the DHW temperature sensor or thermostat This circuit is energized by the boiler with a 5V potential The temperature sensor must be a NTC having 12k 77 F Header Temp Sensor TB1 9 and TB1...

Страница 8: ...re that may cause excessive condensate production in the vent Direct Vent An appliance that is constructed and installed so that all air for combustion is derived directly from outdoors and all flue g...

Страница 9: ...d by deducting the blockage area of any fixed louvers grilles or screens from the total area of the opening 2 Screens shall be not smaller than 3 Motorized louvers shall be interlocked with the applia...

Страница 10: ...echnical Service 1 877 728 5351 INSTALLATION Gas Fired Boiler The boiler vent should not be connected into any portion of another mechanical draft system without consulting the vent manufacturer The b...

Страница 11: ...ll operate at maximum speed Do not operate a summer exhaust fan Close fireplace dampers 4 Place the appliance being inspected in operation Follow the lighting instructions Adjust the thermostat so tha...

Страница 12: ...tted to the boiler The boiler shall not be used as a pipe anchor When installed in a two pipe system that provides both chilled and hot water the control system should be configured so as to limit the...

Страница 13: ...guration 2 Place the boiler in operation at the high fire setting BNR TEST MODE HI 3 Smoothly close the downstream manual isolation valve to reduce the gas flow and cause flame failure 4 The display w...

Страница 14: ...hnician to hold the boiler in high or low fire during firing operation so that the combustion adjustment can be performed as indicated below The second test mode checks the fan rate with the burner of...

Страница 15: ...ssary 3 11 3 Checking Flame Signal Using the control panel enter the information mode and scroll down view the flame signal This shows A when the boiler is firing and shows 0 A when the boiler is not...

Страница 16: ...orrective action or repair 5 1 2 Weekly Observe the conditions of the main flame A normal high fire flame is mostly orange with a blue halo while at low fire the burner will glow yellowish orange Corr...

Страница 17: ...temperature low water level WARNING 5 6 Troubleshooting 5 6 3 Low Gas Pressure The low gas pressure switch opens when there is or has been insufficient gas pressure available for proper operation of...

Страница 18: ...INTERNAL ERROR 31 Internal Error 31 Call for service Code ENVI Display Lockout Description E01 OUT TEMP SENS OPEN Outlet Temperature Sensor Open Boiler outlet water temperature sensor open circuit E02...

Страница 19: ...o not ground through the conduit Terminal Number Label Description 3 120V AC Neutral Neutral for use with TB2 10 Switched Output 4 120V AC Neutral Neutral for use with TB2 11 3 Way Valve 5 120V AC Neu...

Страница 20: ...ly configured for either 208V 220 240V or 440 480V three phase 60 hertz service Improper configuration of the transformer could result in serious injury or death The high voltage TB2 terminal block is...

Страница 21: ...77 728 5351 Gas Fired Boiler 38 Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 Gas Fired Boiler PARTS TECHNICAL SUPPORT PARTS TECHNICAL SUPPORT SC 3000 SC 4000 220 240 VAC three p...

Страница 22: ...1 877 728 5351 Gas Fired Boiler 40 Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 Gas Fired Boiler PARTS TECHNICAL SUPPORT PARTS TECHNICAL SUPPORT 6 1 5 SC 3000 SC 4000 Boiler Wir...

Страница 23: ...lley Technical Service 1 877 728 5351 Gas Fired Boiler 42 Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 Gas Fired Boiler PARTS TECHNICAL SUPPORT PARTS TECHNICAL SUPPORT 6 1 5 2 S...

Страница 24: ...on Kelley Technical Service 1 877 728 5351 Gas Fired Boiler 44 Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 Gas Fired Boiler PARTS TECHNICAL SUPPORT PARTS TECHNICAL SUPPORT 6 1...

Страница 25: ...on Kelley Technical Service 1 877 728 5351 Gas Fired Boiler 46 Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 Gas Fired Boiler PARTS TECHNICAL SUPPORT PARTS TECHNICAL SUPPORT 6 1...

Страница 26: ...5 7 6 4 B 2 4 A Mark Description 1 Heat Exchanger 2 Blower Burner Assembly 3 Base 4 A Gas train LP 4 B Gas Train Natural Gas 5 Controller 6 Electrical Box 7 Front Door Control Panel 8 Cabinet 6 2 1 Ma...

Страница 27: ...Water Connection 5 Condensate Collector 6 Igniter 7 Burner 8 Burner Gasket 9 Burner Hood 6 2 3 SC 3000 SC 4000 Heat Engine Mark Description 1 Burner 2 Burner Transition Piece 3 Blower 4 Venturi 5 Manu...

Страница 28: ...cial or consequential damages such as loss of the use of products facilities or production inconvenience loss of time or labor expense involved in repairing or replacing the alleged defective Product...

Страница 29: ...Date Hi Low Fire O2 CO CO2 Stack Temp pH Action By Appendix 1 Maintenance Log 54 Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 APPENDIX 1 Gas Fired Boiler...

Страница 30: ...in section 3 10 4 to get 5 O2 in the flue gas If this cannot be achieved perform the following steps If the O2 is too high then the inlet gas pressure should be adjusted to the minimum pressure allow...

Страница 31: ...ntire hydronic system Samples of the system water with cleaner should be taken and analyzed to ensure proper cleaner strength Once cleaned the system should be flushed with fresh fill water until the...

Отзывы: