4.
12-position 1734-TOP3 and 1734-TB3 screw lock type termination base assemblies have the following
pins connected internally:
Pin 4 to pin 8
Pin 5 to pin 9
Pin 6 to pin 10
Pin 7 to pin 11
5.
With 8-position 1734-TOP and 1734-TB screw lock termination base assemblies, only use stranded
wire when connecting multiple wires into a single terminal point.
6.
Termination base assembly screw lock wire size range: 14 AWG-22 AWG. Termination base assembly
screw lock wire tightening torque: 7 lb-in [0.6nm] nominal.
7.
8 position 1734-TOPS and 1734-TBS types, and 12 position 1734-TOP3S and 1734-TB3S type, spring
cage contact termination base assemblies may also be used, but are not recommended. If they are
used, connect these termination base assembly types with 14 AWG to 22 AWG stranded wire.