Hardy 1734-WS Installation & Operation Manual
Page | 9
Chapter 2 - Specifications
Chapter 2 lists the specifications for the HI1734-WS Weigh Scale Module. Specifications are listed for the
standard instrument and for optional equipment. The specifications listed are designed to assist in the
installation, operation and troubleshooting of the instrument.
Specifications
Channels:
1
Conversion Rate:
55 updates per second internally, 50 updates per second to PLC.
Averages:
1-255 User Selectable in single increments
Resolution
Internal:
1:8,388,608
Input:
Up to eight (8) 350 ohm Full Wheatstone Bridge, Strain Gauge Load
Sensors/Cells (5 volt excitation) on one scale (using two junction boxes
with a TB-10 connector)
Non-Linearity:
0.001% of Full Scale
Waversaver®:
User
Selectable
Off
7.50 Hz
3.50 Hz
1.00 Hz (Default)
0.50 Hz
0.25 Hz
Backplane Electrical Ratings:
24 VDC, 100 mA
5 VDC, 100 mA
Cable lengths:
250 feet maximum of C2 authorized cable (Maximum of 8 load sensors)
with IT Junction box.
Load Cell Excitation:
5 VDC
Isolation from digital section
1000 VDC minimum
C2 Calibration Output:
Isolation from digital section 1000 VDC minimum
Temperature Drift:
Less than 0.0004% of full scale per degree C for Cal- LO and Cal-HI
reference points
Environmental Requirements
Operating Temperature Range:
-20°C to 55°C (-4°F to 131°F)
Storage Temperature Range:
-40°C to 85°C (-40°F to 185°F)