Technical data
Supply / Charge
Type
1T11
1T22
2T22
2T44
Connection terminals
1x Terminal block, 5 x 6 mm
2
(L1,L2,L3,N,PE)
2x Terminal block, 5 x 6 mm
2
(L1,L2,L3,N,PE)
Rated voltage / frequency
230 V | 400 V 3-phase; 50 Hz
Rated current
16 A
32 A
2x 16 A | 1x 32 A
2x 32 A
Connected load
11 kW
22 kW
44 kW
Charging power max.
11 kW
22 kW
2x 11 kW | 1x 22 kW
2x 22 kW
Charging socket /
charging cable
according
to IEC 62196-2
(automatic socket release in case
of mains voltage failure)
Type 2, 20 A
Type 2, 32 A
2x Type 2, 32 A
Fuse
Type
1T11
1T22
2T22
2T44
DC fault current detection
electronic, DC-RCM, I
Δn,DC
≥6 mA, per charge point
Welding Detection
Error signal via LED indicators
Circuit breaker*
(required on site)
16 A, 3p
32 A, 3p
2x C32 A, 3p |
2x C16 A, 3p
2x 32 A, 3p
Residual current circuit
breaker
(required on site)
RCD type A, 40 A, 30 mA
2x RCD type A, 40 A, 30 mA
**
* C-characteristic recommended
**Special case: with two charging points and one supply line, an RCD type B or type EV is mandatory.
Installation and operating manual
cPH2
charging station
Version: 1.0.9
24