Electrical installation of the charging station
DANGER!
Danger to life due to electric shock!
Before working on the cPH2 charging station:
Disconnect the power supply and ensure that it remains permanently
disconnected during the work.
After completion of the mechanical installation, the charging station is ready to be
connected to the mains. Only the basic connection of the power supply line is described
below: The assembly and connection of optional accessories is not the subject of these
instructions, but is described in the instructions for the respective component.
NOTE!
For the fuse protection of the Wallbox, one
type A RCD
RCD type A
(residual current circuit breaker with 0.03A tripping current)
and a subsequent
circuit breaker 32 A
*
, 3-pole
(C characteristic
recommended) must be pre-installed for each supply line.
**
Special case
:
In the case of a Wallbox with two charging points and only one supply line,
it is mandatory to pre-install a
type B or type EV RCD
in the supply line.
We therefore recommend connecting one supply line per charging point.
*
A C16A or C20A, 3-pole is specified for the cPH2 1T11.
**
Deviating country-specific standards (connection conditions) must be observed!
For the electrical assembly you need the following components:
• Allen key 4 mm (not included in the scope of delivery)
• Stripping pliers for supply cable (not included in scope of delivery)
NOTE!
The initial commissioning of the charging station
MUST ALWAYS
be
carried out by a qualified installer: This person can determine the correct
operation of the charging station or correct any malfunctions or
installation errors.