68 / 154
STRATTON MK3 - Installation, Use and Maintenance
00U07428680-C
Diagram: MK3-3
page 6 / 6
Line No. Value
• Menu
Heating circuit 1/2/3
Adjust the comfort setting
Comfort setpoint temperature
(710/1010/1310)
---°C
Adjust the curve slope
Curve slope (720/1020/1320)
---
Adjust the min. flow temperature for
heating circuit 1
Minimum flow temperature setpoint
(740)
60°C (adjust according
to the lower limit)
Removal of the over-value
Over-value v. mixer (830)
0 °C
Switch the heating regime to permanent comfort
• Domestic hot water
menu
Adjust the DHW setpoint
Comfort setting (1610)
---°C
Activate the DHW mode
Refer to the “ELECTRICAL VALIDATION” chapter for the regulator input/output tests
Refer to the "OPTIMISATION" chapter for configuring the time slots for the heating and DHW circuits
as well as for programming the anti-legionella cycles.
The Navistem B3100's internal heating circuit is deactivated but the settings devices can still be
controlled. This means that all the internal functions of the Navistem B3100 related to heat request calculations
are no longer active (heating curve, ambient influence, ambience controller, daily heating limiter, summer
switching, time programming, operating mode button, accelerated temperature lowering, accelerated heating,
frost protection of rooms, room thermostat, room temperature limit) and must be set on the external Opentherm
thermostat. The Navistem B3100's internal functions, including the status information, are calculated internally
and can therefore have an influence on the other functions in the case of a summer heating limit. This is why it
is important to pay attention to the appropriate setting.
If a heating circuit is controlled by OT, the "AUTO" operating mode is displayed for this circuit. The operating
mode button is blocked for this heating circuit. If the operating mode key is pressed the indication "Operating
mode key blocked" is displayed.
Содержание STRATTON MK3 Series
Страница 2: ......
Страница 13: ...06 02 2023 13 154 STRATTON MK3 Installation Use and Maintenance...
Страница 44: ...44 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C Figure 19 Wiring diagram...
Страница 45: ...06 02 2023 45 154 STRATTON MK3 Installation Use and Maintenance...
Страница 149: ...06 02 2023 149 154 STRATTON MK3 Installation Use and Maintenance...
Страница 150: ...150 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C...
Страница 151: ...06 02 2023 151 154 STRATTON MK3 Installation Use and Maintenance...
Страница 152: ...152 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C...
Страница 153: ...06 02 2023 153 154 STRATTON MK3 Installation Use and Maintenance...