06.02.2023
37 / 154
STRATTON MK3 - Installation, Use and Maintenance
4.5.3. Adjusting the gas valve
- Before starting the burner, on the gas valve,
preset the gas flow rate, using the gas flow rate
adjustment screw Throttle/R1, to the appropriate
value given in the table below.
- Start the burner at maximum power.
- Using a combustion analyser, measure the CO2
ratio in the exhaust gases: on the gas duct,
remove the plug from the opening and insert the
CO2 measurement sensor into the centre of the
flow in the exhaust duct.
- Check the CO2 value at maximum power Qmax
and, if necessary, adjust the gas flow screw
Throttle/R1 of the valve in order to obtain the CO2
values in the table below.
- Change to minimum power Qmin and check that
the CO2 value is within the range in the table
below. If necessary, use the setting adjustment
screw Offset/R2.
- If the setting is adjusted at minimum power, go
back to maximum power Qmax and recheck the
CO2 value. Repeat the operation until both values
comply with the table below.
- Return to the standard operating mode.
After changing the type of gas:
- Check the sealing of the gas line.
- Stick the G31 label provided in place of the
original label (G20).
Figure 12 - STRATTON MK3 40 to 60 setting
Figure 13 - STRATTON MK3 70 to 120 setting
Figure 14 - VR415 for 150 kW model
00U07443960-A
Offset/R2
Throttle/R1
Under cap
Throttle/R1
Offset/R2
00U07446410-A
Throttle/R1
Offset/R2
(Under cap)
Содержание STRATTON MK3 Series
Страница 2: ......
Страница 13: ...06 02 2023 13 154 STRATTON MK3 Installation Use and Maintenance...
Страница 44: ...44 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C Figure 19 Wiring diagram...
Страница 45: ...06 02 2023 45 154 STRATTON MK3 Installation Use and Maintenance...
Страница 149: ...06 02 2023 149 154 STRATTON MK3 Installation Use and Maintenance...
Страница 150: ...150 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C...
Страница 151: ...06 02 2023 151 154 STRATTON MK3 Installation Use and Maintenance...
Страница 152: ...152 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C...
Страница 153: ...06 02 2023 153 154 STRATTON MK3 Installation Use and Maintenance...