120 / 154
STRATTON MK3 - Installation, Use and Maintenance
00U07428680-C
Line
no.
Programming
Access
Default value
Customer setting
Heating circuit 3
1310
Ambient temperature comfort setpoint CCP
U
20 °C
1312
Reduced ambient temperature setpoint CCP
U
18 °C
1314
Ambient setpoint temp. frost protection CCP
U
10 °C
1316
Maximum comfort setpoint CCP
S
35 °C
1320
Heating characteristic slope CCP
U
1.5
1321
Heating characteristic offset CCP
S
0 °C
1326
Heating characteristic translation CCP
S
Stop
1330
Summer/Winter switching temperature CCP
U
19 °C
1332
Daily heating limit CCP
S
-3 °C
1340
Maximum start temperature limitation CCP
M
8 °C
1341
Maximum start temperature limitation CCP
M
80 °C
1342
Room thermostat start temperature CC3
U
65 °C
1350
Ambient temperature influence factor CCP
S
20%
1360
Ambient temperature limitation Heating circuit P
S
1 °C
1361
Terminal regulator heating limit CCP
S
16%
1370
Ambient cons. over-value CCP (accelerated heating)
S
3 °C
1380
Rapid reduction heating circuit P
S
stop
1390
Max. anticipated switch-on time CCP
S
00:00
1391
Max. anticipated switch-off time CCP
S
00:00
1400
Start of increase ambient temperature setpoint CCP
S
-5 °C
1401
End of increase ambient temperature setpoint CCP
S
-15 °C
1420
Overheating protection of CCP to pump
S
on
1430
Mixing valve setpoint over-value CCP
S
3 °C
1432
Servomotor regulation type CCP
S
3 points
1433
Servomotor differential CCP
S
2 °C
1434
Servomotor travel time CCP
S
120 s
1435
Band P (Xp) CCP
S
32 °C
1436
Integration time (Tn) CCP
S
120 s
1450
Screed drying function CCP
M
stop
1451
Manual setpoint for drying concrete screeds CCP
M
25 °C
1461
Over-temperature reduction CC3
S
always
1470
Heating circuit P with buffer tank
S
no
1472
Heating circuit 3 with Pre-regulator/Supply pump
S
no
1481
Wert 5938
S
100%
1482
Min. speed of the CCP pump
S
100%
1483
Max. speed of the CCP pump
S
100%
1500
Operating mode switching heating circuit P
S
protection mode
Domestic hot water
1610
DHW temperature nominal setpoint
U
50 °C
1612
DHW temperature reduced setpoint
S
45 °C
1614
DHW temperature nominal max. setpoint
S
65 °C
1620
DHW release
M
24/24
Содержание STRATTON MK3 Series
Страница 2: ......
Страница 13: ...06 02 2023 13 154 STRATTON MK3 Installation Use and Maintenance...
Страница 44: ...44 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C Figure 19 Wiring diagram...
Страница 45: ...06 02 2023 45 154 STRATTON MK3 Installation Use and Maintenance...
Страница 149: ...06 02 2023 149 154 STRATTON MK3 Installation Use and Maintenance...
Страница 150: ...150 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C...
Страница 151: ...06 02 2023 151 154 STRATTON MK3 Installation Use and Maintenance...
Страница 152: ...152 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C...
Страница 153: ...06 02 2023 153 154 STRATTON MK3 Installation Use and Maintenance...