STRATTON MK3 - Installation, Use and Maintenance
00U07428680-C
BOILER PUMP NOT FROM THE KIT
page 2 / 3
Case of a supplied pump controlled by a 0-10V signal
Connect the pump power supply to terminals 13/14/15 if consumption is <1A, otherwise
connect the power supply to the customer’s electrical cabinet.
The kit (AGU2.551) should be purchased for implementing 0-10V signal control.
To guarantee the temperature at the secondary, it is advisable to place a sensor after the
mixing bottle, the kit reference and its implementation is described below.
Settings on the Navistem B3100
No line Value
• Setup
Menu
Configure the secondary flow sensor (optional)
Sensor input BX2 (5931)
line flow sensor B10
•
Boiler
Menu
Set the minimum rotation speed of the pump
Speed rot. min. pump (2322)
---%
Set the maximum rotation speed of the pump
Speed rot. maxi. pump (2323)
---%
Control accessory required
Quantity
Device reference
Order N°
Mains probe kit
1
QAD 36
059592
{
Option
Secondary bottle sensor (B10)
Содержание STRATTON MK3 Series
Страница 2: ......
Страница 13: ...06 02 2023 13 154 STRATTON MK3 Installation Use and Maintenance...
Страница 44: ...44 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C Figure 19 Wiring diagram...
Страница 45: ...06 02 2023 45 154 STRATTON MK3 Installation Use and Maintenance...
Страница 149: ...06 02 2023 149 154 STRATTON MK3 Installation Use and Maintenance...
Страница 150: ...150 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C...
Страница 151: ...06 02 2023 151 154 STRATTON MK3 Installation Use and Maintenance...
Страница 152: ...152 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C...
Страница 153: ...06 02 2023 153 154 STRATTON MK3 Installation Use and Maintenance...