STRATTON MK3 - Installation, Use and Maintenance
4.3.4.
Assembling the flue
Flue terminals or extension ducts may be cut to shorter lengths if required
When cutting a duct ensure it is square by marking the length all the way
around and only cut back the plain end.
When cutting concentric duct, it is important that the inner duct is maintained
at 20mm longer than the outer duct to allow correct connection of the ducts.
Care should be taken to support the inner duct when cutting the flue. When
assembling only use water as a lubricant.
Note. Horizontal flue runs must be angled down between1.5° - 3° towards
the water heater to allow the condensate to drain. For this reason, it is
recommended that a support bracket is used for every 1m of extension pipe.
See below for flue assembly examples.
Cut the white terminal tube to the correct length and ensure the painted wall
plate is pushed hard up to the black terminal collar when fitted.
IMPORTANT:
There should be NO white terminal tube visible when viewed from the
outside.
Horizontal air
or flue terminal
Extension pipe
Wall tube
Wall plate
Содержание STRATTON MK3 Series
Страница 2: ......
Страница 13: ...06 02 2023 13 154 STRATTON MK3 Installation Use and Maintenance...
Страница 44: ...44 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C Figure 19 Wiring diagram...
Страница 45: ...06 02 2023 45 154 STRATTON MK3 Installation Use and Maintenance...
Страница 149: ...06 02 2023 149 154 STRATTON MK3 Installation Use and Maintenance...
Страница 150: ...150 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C...
Страница 151: ...06 02 2023 151 154 STRATTON MK3 Installation Use and Maintenance...
Страница 152: ...152 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C...
Страница 153: ...06 02 2023 153 154 STRATTON MK3 Installation Use and Maintenance...