36 / 154
STRATTON MK3 - Installation, Use and Maintenance
00U07428680-C
Figure 11 - Installing the propane injector
4.5.2. Changing the ignition, pre-ventilation, minimum and maximum speeds
Place the boiler in standby mode (see § 3.3.1 of the NAVISTEM B3100 boiler
command table instructions).
If necessary, press the ESC button to return to the main screen.
Open the menu
Settings / Safety unit
.
Adjust the pre-ventilation speed (9504), ignition speed (9512), minimum
speed (9524) and maximum speed (9529) settings:
Models
Gas
9504
9512
9524
9529
40
G20
4090
2430
2430
8740
G31
4090
3910
2350
8340
60
G20
4220
3280
2500
9500
G31
4220
3610
2400
9100
70
G20
4930
3160
2540
9500
G31
4930
3260
2400
9000
80
G20
3100
1930
1930
5500
G31
3100
1870
1870
5500
100
G20
3100
1930
1930
6450
G31
3100
1870
1870
6450
120
G20
2900
2120
2070
7400
G31
2900
2360
2000
7200
Nut
Gas valve
Crank flange
screw (x4)
Propane Injector
STRATTON MK3
70 :
ø
6.4
STRATTON MK3
80 / 100 :
ø
6.8
STRATTON MK3
120 :
ø
7.4
Screw (x4)
1
00U07446410-A
Содержание STRATTON MK3 Series
Страница 2: ......
Страница 13: ...06 02 2023 13 154 STRATTON MK3 Installation Use and Maintenance...
Страница 44: ...44 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C Figure 19 Wiring diagram...
Страница 45: ...06 02 2023 45 154 STRATTON MK3 Installation Use and Maintenance...
Страница 149: ...06 02 2023 149 154 STRATTON MK3 Installation Use and Maintenance...
Страница 150: ...150 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C...
Страница 151: ...06 02 2023 151 154 STRATTON MK3 Installation Use and Maintenance...
Страница 152: ...152 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C...
Страница 153: ...06 02 2023 153 154 STRATTON MK3 Installation Use and Maintenance...