100 / 154
STRATTON MK3 - Installation, Use and Maintenance
00U07428680-C
OPTIMISATION
page 4 / 4
DHW CIRCUIT OPTIMISATION
Line No. Value
• DHW tank
menu
Adjust the over value
Start setpoint T° over-value (5020)
16 °C
•
Configuration
menu
Activate the heating circuits' frost
protection mode
Installation frost protection (6120)
on
Setting the anti-legionella cycle (if desired)
• Domestic hot water
menu
Activate anti-legionella mode
Anti-legionella function (1640)
stop / periodic / fixed
day of the week
Choice of repetition. From daily to every 7 days. 1641 = periodic
Periodical anti-legionella function (1641)
1 to 7 days
Choice of day of the week if 1641 = fixed weekday
Legionella function day week (1642)
Monday...Sunday
Anti-legionella launch time
Times of anti-legionella operation (1644)
00:00
Heating T° setpoint for anti-legionella
function
Anti-legionella setpoint (1645)
As needed (°C)
Anti-legionella T° holding time
Anti-legionella function duration (1646)
As needed (min)
Содержание STRATTON MK3 Series
Страница 2: ......
Страница 13: ...06 02 2023 13 154 STRATTON MK3 Installation Use and Maintenance...
Страница 44: ...44 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C Figure 19 Wiring diagram...
Страница 45: ...06 02 2023 45 154 STRATTON MK3 Installation Use and Maintenance...
Страница 149: ...06 02 2023 149 154 STRATTON MK3 Installation Use and Maintenance...
Страница 150: ...150 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C...
Страница 151: ...06 02 2023 151 154 STRATTON MK3 Installation Use and Maintenance...
Страница 152: ...152 154 STRATTON MK3 Installation Use and Maintenance 00U07428680 C...
Страница 153: ...06 02 2023 153 154 STRATTON MK3 Installation Use and Maintenance...