background image

Supplied By www.heating spares.co  Tel. 0161 620 6677

9

A

VAILABLE PUMP HEAD

7

6

5

4

3

2

1

Flow Rate ltr/min

A

vailable Head Metres

2m HEAD

Bth/hr.

kW

Flow rate

t°C

85,000

25.0

17.9 l/m

20.0

75,000

22.0

17.9 l/m

17.6

65,000

19.0

17.9 l/m

15.3

50,000

14.7

17.9 l/m

11.8

7

3.3

FLUE TERMINAL POSITION

Detailed r

ecommendations for flue installation are given in BS

5440:1. The following notes are for general guidance.

a)

The boiler MUST be installed so that the ter

minal is

exposed to the external air.

b)

It is impor

tant that the position of the terminal allows free

passage of air across it at all times.

c) 

It is ESSENTIAL TO ENSURE that pr

oducts of combustion

discharging from the terminal cannot re-enter the building,
or any other adjacent building, through ventilators,
windows, doors, other sources of natural air infiltration, or
forced ventilation/air conditioning.

d)

The minimum acceptable dimensions fr

om the terminal to

obstructions and ventilation openings are specified in Fig.8.

e)

If the ter

minal discharges into a pathway or passageway

check that combustion products will not cause nuisance and
that the terminal will not obstruct the passageway.

f)

Wher

e the lowest part of terminal is fitted less than 2000 mm 

(78 ins) above the ground, above a balcony or above a 
flat roof to which people have access, the terminal MUST 
be protected by a purpose designed terminal guard 
(optional extra; Part No.951505).

g)

The air inlet / flue outlet duct MUST NOT be closer than

25mm (1in) to combustible material.

h)

In cer

tain weather conditions the terminal may emit a

plume of steam. This is normal but positions where this
would cause a nuisance should be avoided.

Detailed recommendations for air supply are given in BS 5440:2.

The following notes are for general guidance.

a)

It is not necessar

y to have a purpose provided air vent in the 

room or internal space in which the appliance is installed.

b)

If the boiler is to be installed in a wall cupboar

d permanent 

air vents are required for cooling purposes in the cupboard at 
both high and low levels. Both air vents must communicate 
with either the same internal room / space or be on the same 
wall to external air. Each air vent communicating with another
room or internal space must have a minimum effective area  
of: 362 cm

2

(56 in

2

)

If the ventilation is direct to air from outside the building, the 
necessary areas quoted above may be halved.

If the cupboar

d or compartment height is 2000 mm

min then NO purpose made ventilation is required. 

GAS SUPPLY

a)

T

he Gas Supplier should be consulted at the installation

planning stage in order to establish the availability of an
adequate supply of gas.

b)

An existing ser

vice pipe MUST NOT be used without prior

consultation with the Gas Supplier.

c)

A gas meter can only be connected by the Gas Supplier or by

their contractor.

d)

An existing meter and/or pipework should be of suf

ficient

size to carry the maximum boiler input plus the demand 
of any other installed appliance. (BS 6891: 1988). 

A minimum of 22 mm dia. pipework is r

equired to

within 1 metre of the appliance gas cock.

e) Natural gas appliances:

The gover

nor at the meter 

must give a constant outlet pressure of 20 mbar (8 in.wg) 
when all appliances on the system are running. 

Pr

opane appliances:

The r

egulator must give a 

constant outlet pressure of 37 mbar (14.9 in.wg) when all
appliances on the system are running.

f)

The gas supply line should be pur

ged. WARNING: Before

purging open all doors and windows, also extinguish any
cigarettes, pipes, and any other naked lights.

g)

The complete installation must be tested for gas soundness

.

3.6

CENTRAL HEATING SYSTEMS

a)

This appliance is designed for connection to sealed central

heating water systems. Refer to Fig. 11 for a typical system
design.

b)

A sealed system must only be filled by a competent person.

c)

The available pump head is given in Fig. 9.

d)

A minimum heating flow rate cor

responding to a heating 

differential of 15°C must be obtained at all times.

e)

An automatic heating bypass is fitted within the appliance.

However if thermostatic radiator valves are fitted, a radiator
must be fitted with two lockshield valves.

f)

The following paragraphs outline the specifications of the

items fitted to the boiler.

PUMP

The available head shown in Fig. 9 is that in excess of the 

appliance hydraulic resistance, i.e. that available for the system.

3.4

3.5

VENTILATION REQUIREMENTS

0

2

4

6

8

10

12

14

16 18

20

22

Содержание Finest Platinum

Страница 1: ...FINEST PLATINUM P R E M I U M P E R F O R M A N C E C O M B I B O I L E R INSTALLATION AND SERVICING INSTRUCTIONS TO BE GIVEN TO THE USER 0086 EC 0087 BO 33 G C Appliance No 47 260 02 Finest Platinum...

Страница 2: ...ator is fitted with lockshield valves normally in the bathroom to allow pump overrun circulation Internal frost protection is fitted as standard equipment The boiler may be used with any certified mai...

Страница 3: ...iance is certified to comply with the requirements of EN 483 and EN 625 for use in GB and IE Great Britain and Ireland using the following gas categories Finest Platinum I2H G20 with a governed gas su...

Страница 4: ...e maximum minimum permissible allowable length of the flue system is Horizontal flue terminal Right and Left maximum 2500 mm 99 in Horizontal flue terminal Rear maximum 2000 mm 79 in Horizontal flue t...

Страница 5: ...L SOCKET 3 Fig 3 b Offset vertical flue a measured from the boiler centre line to the centre line of the extension elbow b measured from the centre line of the extension elbow to the underside of the...

Страница 6: ...Supplied By www heating spares co Tel 0161 620 6677 6 EXPLODED DIAGRAM for key no references see spare parts catalogue Drawing amended June 03 4...

Страница 7: ...ater IN Plate Heat Exchanger Overheat Stat DHW out Heating Flow By Pass 3 bar Pressure Relief Valve DOMESTIC HOT WATER MODE AUTOMATIC AIR VENT EXPANSION VESSEL Heating Return PRESSURE GAUGE PUMP Cold...

Страница 8: ...d Use Regulations The appropriate Building Regulations either The Building Regulations The Building Regulations Scotland Building Regulations Northern Ireland The Water Fittings Regulations or Water b...

Страница 9: ...ernal room space or be on the same wall to external air Each air vent communicating with another room or internal space must have a minimum effective area of 362 cm2 56 in2 If the ventilation is direc...

Страница 10: ...UIREMENTS Vessel charge and initial system pressure Total water content of system using 8ltr 1 54gal capacity expansion vessel supplied with appliance For systems having a larger capacity multiply the...

Страница 11: ...PEN POSITION PRESSURE RELIEF VALVE OUTLET TO DRAIN DOMESTIC HOT WATER DOMESTIC COLD WATER PRESSURE REDUCING VALVE IF REQUIRED BS STOP VALVE FIXED SPINDLE MAINS WATER DRAIN COCK AT LOWEST POINT S OF SY...

Страница 12: ...s are achieved Ensure squareness by hanging a plumbline b Mark the position of the wall mounting plate fixing holes 4 Select one from each group Refer to Fig 12 c Mark the position of the flue outlet...

Страница 13: ...ral heating system to the boiler flow and return isolating valves 13 DETERMINING THE POSITION OF THE AIR FLUE DUCT HOLE 14 4 4 SERVICE CONNECTIONS 4 3 MOUNTING THE BOILER 225mm 225mm 95mm 13 b SIDE FL...

Страница 14: ...e an adequate seal The wall liner is a tube diameter 130mm with a wall thickness of 0 8mm a Measure the required flue length as shown in Figure 16 Refer to section 2 5 to determine whether any extensi...

Страница 15: ...ON ON AIR DUCT 767mm EXTENSION MIN OVERLAP 50mm 2in 425mm L 76mm MAX 319mm TOP 17mm 17 AIR FLUE DUCT ASSEMBLY STANDARD DUCT Fits Outside Elbow EXTENSION DUCT S Fits Over Duct STANDARD TERMINAL Fits In...

Страница 16: ...e carton as the appliance are to be used fit the restrictor as follows a Note the position of the flue restrictor ring This is fitted on top of the appliance and is secured by the air pressure switch...

Страница 17: ...ue system towards the boiler to seat the external sealing ring against the outside wall and secure the air duct to the elbow using the two screws provided e Finally use the internal sealing ring to ma...

Страница 18: ...rough the clamping arrangement The cable will be held in position as the plug cover is fitted If a room thermostat is to be fitted remove the red link between L2 and L3 and connect the thermostat acro...

Страница 19: ...em air vents in accordance with normal practice Ensure that all system air vents are closed NOTE The boiler is supplied with a filling loop and fittings 3 Check the system for soundness 4 Check the op...

Страница 20: ...h Ensure that the room thermostat if fitted is calling for heat Turn the clock override switch to the I position Turn the CH temperature control knob to the position The boiler will perform a series...

Страница 21: ...from firing if there is inadequate water flow through the main heat exchanger DHW PRE HEAT DHW Comfort selected With no demand for DHW the boiler will fire periodically for a few seconds to maintain t...

Страница 22: ...lide the burner out of the combustion chamber g Inspect and if necessary clean the main burner ports using a soft brush or vacuum cleaner Do not use a wire brush or any abrasive material Check that th...

Страница 23: ...sembled into the injector Refer to Fig 30 Check that all joints and seals are correctly fitted Note that fan polarity is immaterial a Slacken the screw in the burner pressure test point and connect a...

Страница 24: ...Supplied By www heating spares co Tel 0161 620 6677 22 INTERNAL WIRING DIAGRAMS 7 7 1 FUNCTIONAL FLOW WIRING DIAGRAM...

Страница 25: ...T FINDING In the event of the boiler failing to light refer to the Diagnostics Chart Detailed procedures for replacing faulty components are described in section 9 Parts Replacement For further inform...

Страница 26: ...heir position e Remove the fan assembly 3 screws and withdraw the assembly by lowering and lifting it forwards f Fit the new fan assembly and re assemble in reverse order Ensure that all joints and se...

Страница 27: ...aint re applied to seal it 9 6 AIR PRESSURE SWITCH Refer to Fig 29 a Ensure supply voltage is isolated b Remove the casing front panel and sealed chamber front panel Refer to section 9 3 c Disconnect...

Страница 28: ...ection 9 12 d Remove the two spring clips securing the bypass pipe and pull out the pipe e Remove the two socket screws securing the heat exchanger to the water manifolds and push the heat exchanger d...

Страница 29: ...nion connections and remove the valve d Fit the new valve and re assemble in reverse order e Re commission the system Refer to section 5 9 20 MAIN HEAT EXCHANGER Refer to Fig 29 a Remove the casing fr...

Страница 30: ...MBLY 1 601012 9 DHW FLOWSWITCH Hall effect Sensor 1 500641 10a CH O HEAT THERMISTOR 1 550530 10b DHW THERMISTOR 1 500590 11 MAIN HEAT EXCHANGER 1 450984 12 DHW HEAT EXCHANGER 1 451011 13 PRESSURE RELI...

Страница 31: ...or less For fitting instructions refer to Fig 22 The flue restrictor supplied with the appliance must not be used and should be discarded a Read the installation requirements and flue specifications d...

Страница 32: ...ephone 01787 272800 Sales Direct Line 01787 475557 Fax 01787 474588 Service Helpline 01926 834834 Training 01926 834838 Email sales halsteadboilers co uk or service halsteadboilers co uk or training h...

Отзывы: