2

SPECIFICA

TION FOR STANDARD AND SIDE HORIZONTAL FLUES

(Refer to section 2.6(b) for maximum allowable lengths)

‘L

‘S’

‘L’

‘R’

2(a)

‘L(i)’

‘L(ii)’

2(b)

Fig 2a - Standard flue assembly using either
side or rear outlet.

L measur

ed from the centre line of boiler flue outlet to 

outside wall face = max 820 mm
R measured from the centre line of boiler flue outlet to rear
of boiler = 201 mm
S measured from the centre line of boiler flue outlet to side
of boiler = 226 mm
(Allow for minimum clearance of 5 mm at side of boiler)

No flue r

estrictors should be used if the flue

length exceeds 620 mm.

Fig 2b - Standard flue assembly with
optional straight extensions using either
side or rear outlet

Maximum flue length ‘L(i)’ (measur

ed from the boiler

outlet centre line to the outside wall face).
Finest Platinum = 2500mm (99in)

Maximum flue length ‘L(ii)’ (measured from the boiler
outlet centre line to the outside wall face).
Finest Platinum = 2000mm (79in)

2

V

ertical Roof Terminal

For use wher

e an external wall is not

available. For installation details, refer to Supplement 1 at the rear of
this booklet.

These optional kits may be used with the standard flue kit to
produce an extensive range of flue options. Examples are
illustrated in Figures 2 and 3. Variations upon these illustrations
may be used providing that the following rules are strictly obeyed.

a)

The maximum/minimum per

missible allowable length of the flue

system is:

Horizontal flue terminal (Right and Left) - maximum 2500 mm (99 in) 
Horizontal flue terminal (Rear)

- maximum 2000 mm (79 in)

Horizontal flue terminal 

- minimum  300 mm (12 in)

Vertical flue terminal

- maximum 4000 mm (158 in)

Vertical flue terminal

- minimum 565 mm (22 in) 

b)

The standar

d terminal must always be fitted horizontally. The vertical

terminal must always be used if a vertical outlet is required.

c) 

The flue must only ter

minate in a horizontal or vertical position. 

However, 90° flue elbows may be used to drop the height of 
the flue system by 500 mm.

2.5

CONCENTRIC AIR/FLUE DUCT SPECIFICATIONS

The appliance is supplied complete with a standar

d telescopic flue

kit. This comprises a standard duct and a terminal duct and can be
used for flue lengths between 506 mm and 820 mm without cutting
the ducts. To use terminal duct for flue length between 300 and 506
mm the ducts need cutting. Avoid swarf and sharp edges to maintain
telescopic function

The following additional concentric kits are available as optional
extras.

Extension duct

(each extension extends the flue length by up to

767 mm)

90

° Extension Elbow

(Allows an additional bend in the flue and

has an ‘equivalent length’ of 767 mm.) This elbow is mechanically
different from the flanged elbow supplied as standard with the
appliance, but has the same equivalent length of 767 mm. 

45

° Extension Elbow

Allows an additional bend in the flue and

has an equivalent length of 384 mm. 

V

ertical Turret Socket

For use with elevated horizontal flues and

vertical cowls.

Содержание Finest Platinum

Страница 1: ...FINEST PLATINUM P R E M I U M P E R F O R M A N C E C O M B I B O I L E R INSTALLATION AND SERVICING INSTRUCTIONS TO BE GIVEN TO THE USER 0086 EC 0087 BO 33 G C Appliance No 47 260 02 Finest Platinum...

Страница 2: ...ator is fitted with lockshield valves normally in the bathroom to allow pump overrun circulation Internal frost protection is fitted as standard equipment The boiler may be used with any certified mai...

Страница 3: ...iance is certified to comply with the requirements of EN 483 and EN 625 for use in GB and IE Great Britain and Ireland using the following gas categories Finest Platinum I2H G20 with a governed gas su...

Страница 4: ...e maximum minimum permissible allowable length of the flue system is Horizontal flue terminal Right and Left maximum 2500 mm 99 in Horizontal flue terminal Rear maximum 2000 mm 79 in Horizontal flue t...

Страница 5: ...L SOCKET 3 Fig 3 b Offset vertical flue a measured from the boiler centre line to the centre line of the extension elbow b measured from the centre line of the extension elbow to the underside of the...

Страница 6: ...Supplied By www heating spares co Tel 0161 620 6677 6 EXPLODED DIAGRAM for key no references see spare parts catalogue Drawing amended June 03 4...

Страница 7: ...ater IN Plate Heat Exchanger Overheat Stat DHW out Heating Flow By Pass 3 bar Pressure Relief Valve DOMESTIC HOT WATER MODE AUTOMATIC AIR VENT EXPANSION VESSEL Heating Return PRESSURE GAUGE PUMP Cold...

Страница 8: ...d Use Regulations The appropriate Building Regulations either The Building Regulations The Building Regulations Scotland Building Regulations Northern Ireland The Water Fittings Regulations or Water b...

Страница 9: ...ernal room space or be on the same wall to external air Each air vent communicating with another room or internal space must have a minimum effective area of 362 cm2 56 in2 If the ventilation is direc...

Страница 10: ...UIREMENTS Vessel charge and initial system pressure Total water content of system using 8ltr 1 54gal capacity expansion vessel supplied with appliance For systems having a larger capacity multiply the...

Страница 11: ...PEN POSITION PRESSURE RELIEF VALVE OUTLET TO DRAIN DOMESTIC HOT WATER DOMESTIC COLD WATER PRESSURE REDUCING VALVE IF REQUIRED BS STOP VALVE FIXED SPINDLE MAINS WATER DRAIN COCK AT LOWEST POINT S OF SY...

Страница 12: ...s are achieved Ensure squareness by hanging a plumbline b Mark the position of the wall mounting plate fixing holes 4 Select one from each group Refer to Fig 12 c Mark the position of the flue outlet...

Страница 13: ...ral heating system to the boiler flow and return isolating valves 13 DETERMINING THE POSITION OF THE AIR FLUE DUCT HOLE 14 4 4 SERVICE CONNECTIONS 4 3 MOUNTING THE BOILER 225mm 225mm 95mm 13 b SIDE FL...

Страница 14: ...e an adequate seal The wall liner is a tube diameter 130mm with a wall thickness of 0 8mm a Measure the required flue length as shown in Figure 16 Refer to section 2 5 to determine whether any extensi...

Страница 15: ...ON ON AIR DUCT 767mm EXTENSION MIN OVERLAP 50mm 2in 425mm L 76mm MAX 319mm TOP 17mm 17 AIR FLUE DUCT ASSEMBLY STANDARD DUCT Fits Outside Elbow EXTENSION DUCT S Fits Over Duct STANDARD TERMINAL Fits In...

Страница 16: ...e carton as the appliance are to be used fit the restrictor as follows a Note the position of the flue restrictor ring This is fitted on top of the appliance and is secured by the air pressure switch...

Страница 17: ...ue system towards the boiler to seat the external sealing ring against the outside wall and secure the air duct to the elbow using the two screws provided e Finally use the internal sealing ring to ma...

Страница 18: ...rough the clamping arrangement The cable will be held in position as the plug cover is fitted If a room thermostat is to be fitted remove the red link between L2 and L3 and connect the thermostat acro...

Страница 19: ...em air vents in accordance with normal practice Ensure that all system air vents are closed NOTE The boiler is supplied with a filling loop and fittings 3 Check the system for soundness 4 Check the op...

Страница 20: ...h Ensure that the room thermostat if fitted is calling for heat Turn the clock override switch to the I position Turn the CH temperature control knob to the position The boiler will perform a series...

Страница 21: ...from firing if there is inadequate water flow through the main heat exchanger DHW PRE HEAT DHW Comfort selected With no demand for DHW the boiler will fire periodically for a few seconds to maintain t...

Страница 22: ...lide the burner out of the combustion chamber g Inspect and if necessary clean the main burner ports using a soft brush or vacuum cleaner Do not use a wire brush or any abrasive material Check that th...

Страница 23: ...sembled into the injector Refer to Fig 30 Check that all joints and seals are correctly fitted Note that fan polarity is immaterial a Slacken the screw in the burner pressure test point and connect a...

Страница 24: ...Supplied By www heating spares co Tel 0161 620 6677 22 INTERNAL WIRING DIAGRAMS 7 7 1 FUNCTIONAL FLOW WIRING DIAGRAM...

Страница 25: ...T FINDING In the event of the boiler failing to light refer to the Diagnostics Chart Detailed procedures for replacing faulty components are described in section 9 Parts Replacement For further inform...

Страница 26: ...heir position e Remove the fan assembly 3 screws and withdraw the assembly by lowering and lifting it forwards f Fit the new fan assembly and re assemble in reverse order Ensure that all joints and se...

Страница 27: ...aint re applied to seal it 9 6 AIR PRESSURE SWITCH Refer to Fig 29 a Ensure supply voltage is isolated b Remove the casing front panel and sealed chamber front panel Refer to section 9 3 c Disconnect...

Страница 28: ...ection 9 12 d Remove the two spring clips securing the bypass pipe and pull out the pipe e Remove the two socket screws securing the heat exchanger to the water manifolds and push the heat exchanger d...

Страница 29: ...nion connections and remove the valve d Fit the new valve and re assemble in reverse order e Re commission the system Refer to section 5 9 20 MAIN HEAT EXCHANGER Refer to Fig 29 a Remove the casing fr...

Страница 30: ...MBLY 1 601012 9 DHW FLOWSWITCH Hall effect Sensor 1 500641 10a CH O HEAT THERMISTOR 1 550530 10b DHW THERMISTOR 1 500590 11 MAIN HEAT EXCHANGER 1 450984 12 DHW HEAT EXCHANGER 1 451011 13 PRESSURE RELI...

Страница 31: ...or less For fitting instructions refer to Fig 22 The flue restrictor supplied with the appliance must not be used and should be discarded a Read the installation requirements and flue specifications d...

Страница 32: ...ephone 01787 272800 Sales Direct Line 01787 475557 Fax 01787 474588 Service Helpline 01926 834834 Training 01926 834838 Email sales halsteadboilers co uk or service halsteadboilers co uk or training h...

Отзывы: