background image

Supplied By www.heating spares.co  Tel. 0161 620 6677

18

5.2

COMMISSIONING THE APPLIANCE

Refer to Fig. 25

Note:

If, at any time during the commissioning procedure, it is required

to prevent the boiler from modulating, set the CH temperature control
knob to the Service position.

a)

Check that the gas supply is tur

ned ON and the gas service cock is 

OPEN.

b)

Slacken the scr

ew in the burner pressure test point and connect a 

suitable manometer. Refer to Fig. 30.

c)

Set the DHW and CH temperatur

e control knobs fully anti-

clockwise to the standby positions.

d)

T

urn on the electrical supply and set the ON/OFF switch to ON (I).

The 

Reset

LED will briefly show r

ed, then blue, then extinguish.

The fan will start briefly and then stop.
The LEDs 1-4 (yellow) will illuminate briefly.

e)

T

urn the DHW temperature control knob to the desired temperature 

position and fully open any DHW tap.  LED 1 will show yellow 
(

Economy

mode). The ignition sequence will commence and 

when flame is detected the 

Reset

LED will show blue. 

If the burner fails to light after five attempts, ignition lock-out occurs.
In this event the 

Reset

LED will show RED. 

To re-set the appliance and initiate a further ignition sequence, 
press the 

Reset

button.

Note:  

If the 

Reset

LED show RED, to establish the cause press and hold

the 

Reset

button for three seconds. 

The 

Reset

LED will flash RED and

the error code will be displayed via the LED’s 1-4.

f)

After ignition, allow the boiler to r

un for at least 10 minutes and 

check that the burner pressure is as stated on the data badge ±10 %.
(Nat. gas 15.5 mbar 39.6 kW or 135115 Btu/h gross heat input, 
Propane 23.4 mbar or 120068 Btu/h). The DHW burner pressure 
is factory set and should not require adjusting. If the burner pressure 
is low, check that the appliance has not started to modulate (This will
occur if the DHW flow rate is low. If modulation is suspected, open 
all DHW taps to maximise the flow and re-check the  burner 
pressure). If it is necessary to adjust the burner pressure the method 
is described in section 9.5 ‘Gas valve replacement’.

Note:

T

o select 

Comfor

t

DHW control, ie with pre-heat, turn the 

DHW temperature control knob fully clockwise and then back to the 
desired temperature setting. LED 2 will then illuminate and LED 1 
extinguish.

g)

Close the DHW tap and ensur

e that the burner goes out (BLUE 

light off) and the pump stops after an over-run period of 5 minutes.

h)

Ensur

e that the room thermostat (if fitted) is calling for heat.

Turn the clock override switch to the ‘I’ position Turn the CH 
temperature control knob to the ‘+’ position.
The boiler will perform a series of self-checks, light and then 
go to minimum rate burner pressure(Nat. gas 3 mbar, propane 
5.8 mbar).  After ignition,  the burner pressure will remain at this 
for about ten minutes, before ramping up to the factory set burner 
pressure, or to a modulated value if the system is hot.
The 

Reset

LED will show BLUE and LEDs 3 and 4 will show 

YELLOW. 

i)

Set the clock to the desir

ed times by setting the tabs.

j)

Slide the clock over

ride switch to the 'timed' position 

and 

check the operation of the clock and room thermostat (If fitted) 

Caution:

W

ith the CH temperature control knob in the Service position,

the boiler will fire continuously at full output and LEDs 3 and 4 will flash.
This setting is for the convenience of the Service Engineer ONLY.

Mains ON/OFF

Switch

CH Error Code

Indicator (3&4)

CH Temp.

Control

DHW Economy/

Comfort Switch

Economy/Comfort

Error Code LED (1&2)

Service Function

24hr Clock

BURNER (Blue)

LOCK-OUT (Red)

LED and

Reset Button

Pr

essure

Gauge

DHW

Temperature

Control

ARROW 

INDICATES

CURRENT TIME

T

ABS OUT 

ON

PERIOD

T

ABS IN 

OFF

PERIOD

CLOCK OVERRIDE 

SWITCH (Heating only)

= Continuous ON
= Timed
= OFF

27

F

ASCIA PANEL AND CONTROLS

• •

5.3

DOMESTIC HOT WATER FLOWRATE

A flow r

egulator is supplied factory fitted to the appliance to ensure that

no adjustment is necessary. Should the mains flow rate be below the
minimum required, it is possible to remove the flow regulator from the
appliance as instructed in section 9. The nominal pre-adjusted flow rate
may vary by ± 5 % due to factory tolerances and mains water pressure
fluctuation.

5.4

FINAL CHECKS

a) 

T

urn both the DHW and CH temperature control knobs to standby.

b)

T

urn the appliance on/off switch to the off (o) position, remove 

the manometer and tighten the burner pressure test point screw. 
Re-light the burner and test for gas tightness.

c)

Fit the boiler casing as described and illustrated in Figur

e 28: Fit each 

side panel with two screws at the top and bottom of each panel.  Position
and fit controls cover in place using screws provided.  Ensure it hinges 
correctly.  Fit the front panel in position using locating studs and ensure 
correctly seated by pressing.

d)

Set the heating and hot water contr

ols to the required settings. 

Ensure that the clock override switch is in the timed position and check 
that the time clock is set at the desired time periods. Set the room 
thermostat (if fitted) to the required setting.

Содержание Finest Platinum

Страница 1: ...FINEST PLATINUM P R E M I U M P E R F O R M A N C E C O M B I B O I L E R INSTALLATION AND SERVICING INSTRUCTIONS TO BE GIVEN TO THE USER 0086 EC 0087 BO 33 G C Appliance No 47 260 02 Finest Platinum...

Страница 2: ...ator is fitted with lockshield valves normally in the bathroom to allow pump overrun circulation Internal frost protection is fitted as standard equipment The boiler may be used with any certified mai...

Страница 3: ...iance is certified to comply with the requirements of EN 483 and EN 625 for use in GB and IE Great Britain and Ireland using the following gas categories Finest Platinum I2H G20 with a governed gas su...

Страница 4: ...e maximum minimum permissible allowable length of the flue system is Horizontal flue terminal Right and Left maximum 2500 mm 99 in Horizontal flue terminal Rear maximum 2000 mm 79 in Horizontal flue t...

Страница 5: ...L SOCKET 3 Fig 3 b Offset vertical flue a measured from the boiler centre line to the centre line of the extension elbow b measured from the centre line of the extension elbow to the underside of the...

Страница 6: ...Supplied By www heating spares co Tel 0161 620 6677 6 EXPLODED DIAGRAM for key no references see spare parts catalogue Drawing amended June 03 4...

Страница 7: ...ater IN Plate Heat Exchanger Overheat Stat DHW out Heating Flow By Pass 3 bar Pressure Relief Valve DOMESTIC HOT WATER MODE AUTOMATIC AIR VENT EXPANSION VESSEL Heating Return PRESSURE GAUGE PUMP Cold...

Страница 8: ...d Use Regulations The appropriate Building Regulations either The Building Regulations The Building Regulations Scotland Building Regulations Northern Ireland The Water Fittings Regulations or Water b...

Страница 9: ...ernal room space or be on the same wall to external air Each air vent communicating with another room or internal space must have a minimum effective area of 362 cm2 56 in2 If the ventilation is direc...

Страница 10: ...UIREMENTS Vessel charge and initial system pressure Total water content of system using 8ltr 1 54gal capacity expansion vessel supplied with appliance For systems having a larger capacity multiply the...

Страница 11: ...PEN POSITION PRESSURE RELIEF VALVE OUTLET TO DRAIN DOMESTIC HOT WATER DOMESTIC COLD WATER PRESSURE REDUCING VALVE IF REQUIRED BS STOP VALVE FIXED SPINDLE MAINS WATER DRAIN COCK AT LOWEST POINT S OF SY...

Страница 12: ...s are achieved Ensure squareness by hanging a plumbline b Mark the position of the wall mounting plate fixing holes 4 Select one from each group Refer to Fig 12 c Mark the position of the flue outlet...

Страница 13: ...ral heating system to the boiler flow and return isolating valves 13 DETERMINING THE POSITION OF THE AIR FLUE DUCT HOLE 14 4 4 SERVICE CONNECTIONS 4 3 MOUNTING THE BOILER 225mm 225mm 95mm 13 b SIDE FL...

Страница 14: ...e an adequate seal The wall liner is a tube diameter 130mm with a wall thickness of 0 8mm a Measure the required flue length as shown in Figure 16 Refer to section 2 5 to determine whether any extensi...

Страница 15: ...ON ON AIR DUCT 767mm EXTENSION MIN OVERLAP 50mm 2in 425mm L 76mm MAX 319mm TOP 17mm 17 AIR FLUE DUCT ASSEMBLY STANDARD DUCT Fits Outside Elbow EXTENSION DUCT S Fits Over Duct STANDARD TERMINAL Fits In...

Страница 16: ...e carton as the appliance are to be used fit the restrictor as follows a Note the position of the flue restrictor ring This is fitted on top of the appliance and is secured by the air pressure switch...

Страница 17: ...ue system towards the boiler to seat the external sealing ring against the outside wall and secure the air duct to the elbow using the two screws provided e Finally use the internal sealing ring to ma...

Страница 18: ...rough the clamping arrangement The cable will be held in position as the plug cover is fitted If a room thermostat is to be fitted remove the red link between L2 and L3 and connect the thermostat acro...

Страница 19: ...em air vents in accordance with normal practice Ensure that all system air vents are closed NOTE The boiler is supplied with a filling loop and fittings 3 Check the system for soundness 4 Check the op...

Страница 20: ...h Ensure that the room thermostat if fitted is calling for heat Turn the clock override switch to the I position Turn the CH temperature control knob to the position The boiler will perform a series...

Страница 21: ...from firing if there is inadequate water flow through the main heat exchanger DHW PRE HEAT DHW Comfort selected With no demand for DHW the boiler will fire periodically for a few seconds to maintain t...

Страница 22: ...lide the burner out of the combustion chamber g Inspect and if necessary clean the main burner ports using a soft brush or vacuum cleaner Do not use a wire brush or any abrasive material Check that th...

Страница 23: ...sembled into the injector Refer to Fig 30 Check that all joints and seals are correctly fitted Note that fan polarity is immaterial a Slacken the screw in the burner pressure test point and connect a...

Страница 24: ...Supplied By www heating spares co Tel 0161 620 6677 22 INTERNAL WIRING DIAGRAMS 7 7 1 FUNCTIONAL FLOW WIRING DIAGRAM...

Страница 25: ...T FINDING In the event of the boiler failing to light refer to the Diagnostics Chart Detailed procedures for replacing faulty components are described in section 9 Parts Replacement For further inform...

Страница 26: ...heir position e Remove the fan assembly 3 screws and withdraw the assembly by lowering and lifting it forwards f Fit the new fan assembly and re assemble in reverse order Ensure that all joints and se...

Страница 27: ...aint re applied to seal it 9 6 AIR PRESSURE SWITCH Refer to Fig 29 a Ensure supply voltage is isolated b Remove the casing front panel and sealed chamber front panel Refer to section 9 3 c Disconnect...

Страница 28: ...ection 9 12 d Remove the two spring clips securing the bypass pipe and pull out the pipe e Remove the two socket screws securing the heat exchanger to the water manifolds and push the heat exchanger d...

Страница 29: ...nion connections and remove the valve d Fit the new valve and re assemble in reverse order e Re commission the system Refer to section 5 9 20 MAIN HEAT EXCHANGER Refer to Fig 29 a Remove the casing fr...

Страница 30: ...MBLY 1 601012 9 DHW FLOWSWITCH Hall effect Sensor 1 500641 10a CH O HEAT THERMISTOR 1 550530 10b DHW THERMISTOR 1 500590 11 MAIN HEAT EXCHANGER 1 450984 12 DHW HEAT EXCHANGER 1 451011 13 PRESSURE RELI...

Страница 31: ...or less For fitting instructions refer to Fig 22 The flue restrictor supplied with the appliance must not be used and should be discarded a Read the installation requirements and flue specifications d...

Страница 32: ...ephone 01787 272800 Sales Direct Line 01787 475557 Fax 01787 474588 Service Helpline 01926 834834 Training 01926 834838 Email sales halsteadboilers co uk or service halsteadboilers co uk or training h...

Отзывы: