background image

Supplied By www.heating spares.co  Tel. 0161 620 6677

PARTS REPLACEMENT

9

9.2

FAN ASSEMBLY

9.3

BURNER

9.4

IGNITION & DETECTION ELECTRODES

9.5

MULTIFUNCTIONAL GAS CONTROL

9.5.1

GAS CONTROL REPLACEMENT

The design of the appliance is such that the combustion chamber

insulation should not require replacement unless mechanically

damaged. It is recommended that to prevent dust, the insulation is

dampened prior to removal.

a)

Remove the r

etaining screw and lift off the casing front panel. 

Refer to Fig.28

b)

Remove the sealed chamber fr

ont panel (4 screws).

c)

Remove the combustion chamber fr

ont panel (9 screws).

The front insulation may now be replaced, but to replace the side and

rear insulation, the heat exchanger must be removed. Refer to section X

d)

Fit the new insulation and r

e-assemble in reverse order. 

e)

Ensur

e that all joints and seals are correctly re-fitted and re-

commission the system (if necessary) using the procedure in 

section 5.1.

It is r

ecommended that a protective mask is worn when

changing or handling the insulation material.

a)

Remove the casing fr

ont panel. Refer to Fig. 31

b

)

Remove the sealed chamber front panel (4 screws).

c)

Remove the combustion chamber fr

ont panel (9 screws). Take 

care not to damage the insulation.

d)

Lower the contr

ols front cover panel and remove the two 

securing screws and lower the controls fascia panel.

e)

Disconnect the thr

ee leads from the spark and detection 

electrodes and disengage the grommets from the combustion 

chamber bottom panel.

f)

Remove the four scr

ews securing the burner to the gas 

manifold and slide the burner out of the combustion chamber.

g)

T

ransfer the ignition and detection electrodes to the new 

burner and check their alignment. Refer to Fig.34.

h)

Fit the new bur

ner and reassemble in reverse order. Ensure 

that all joints and seals are correctly re-fitted.

Refer to Fig. 29

a)

Ensur

e supply voltage is isolated.  Remove the burner. Refer to

section 9.3.

b)

Fit the new ignition and /or detection electr

ode(s) and check 

that both electrodes are aligned as detailed in Fig.34. 

c)

Re-assemble in r

everse order. Ensure that all joints and seals 

are correctly re-fitted.

Refer to Fig. 29

a)

Ensur

e supply voltage is isolated.

b)

Remove the casing fr

ont panel, sealed chamber panel and 

combustion chamber panel. Refer to section 9.3

c)

Car

efully disconnect the two electrical leads from the fan.

d)

Disconnect the air pr

essure switch sensing pipes from the fan, 

noting their position.

e)

Remove the fan assembly  (3 scr

ews) and withdraw the 

assembly by lowering and lifting it forwards.

f)

Fit the new fan assembly and r

e-assemble in reverse order.

Ensure that all joints and seals are correctly re-fitted. (Polarity is

immaterial on the fan connections.)

Before commencing any service operation, ISOLATE the mains electrical
supply and TURN OFF the gas supply at the main service cock.
It is the law that any service work must be carried out by a registered
person.

9.1

COMBUSTION CHAMBER
INSULATION

24

8.4

DHW FAULT FINDING

8.5

CENTRAL HEATING FAULT FINDING

When the hot water tap is tur

ned on, the controls should carry out

a set of start up checks followed by an ignition sequence. Refer to

section 5.2 
If the control has powered up correctly but does not respond to a

DHW demand.
Check operation of fan and air pressure switch. Check if Red LED

on DHW flow switch is on or off.  If off, check DHW hall effect

sensor and condition of sanitary flow detector in hydraulic group

set.  If on, check wires to flow switch, check DHW thermistor and

wires.  If fan, air pressure switch, DHW flow switch, thermistor

and wires are OK replace PCB. 
Guidance notes (Refer to section 7.1):
If DHW temperature heavily fluctuates during a long draw off and

occasionally goes to an overheat Lock-out condition, check the

secondary plate heat exchanger for debris and replace.

Upon a demand for Central Heating, (closure of the time switch and

room thermostat, if fitted) , the controls should carry out a set of start up

checks, followed by an ignition sequence. Refer to Section 5.2.
If the control has powered up correctly but does not respond to a CH

demand. Check voltage between pin 2 plug X1A (orange wire) and

pin 2 X13 (blue wire).  If 0V ac, check room thermostat and clock.  If

230 V ac, check operation of fan and air pressure switch.  Check

operation of gas valve.  If room thermostat clock, fan, air pressure

switch and gas valve are OK replace PCB.
Guidance notes (Refer to section 7.1):
1) Whenever a CH demand is removed, either by the timer, the room

thermostat or the boiler internal temperature control, an anti cycle mode

is initiated which prevents the boiler from firing in CH mode for 3

minutes.  Ensure that the control is not in this mode by removing power

from the control and restoring it after a delay of 10 seconds.

Refer to Figs. 32 and 35

a)

Ensur

e supply voltage is isolated.

b)

Lower the contr

ols front cover panel and remove the casing 

front panel. Refer to section 9.3

c)

Remove the two r

etaining screws and lower the controls 

fascia panel.

d)

Release the scr

ew and unplug the electrical lead from the 

gas control.

Содержание Finest Platinum

Страница 1: ...FINEST PLATINUM P R E M I U M P E R F O R M A N C E C O M B I B O I L E R INSTALLATION AND SERVICING INSTRUCTIONS TO BE GIVEN TO THE USER 0086 EC 0087 BO 33 G C Appliance No 47 260 02 Finest Platinum...

Страница 2: ...ator is fitted with lockshield valves normally in the bathroom to allow pump overrun circulation Internal frost protection is fitted as standard equipment The boiler may be used with any certified mai...

Страница 3: ...iance is certified to comply with the requirements of EN 483 and EN 625 for use in GB and IE Great Britain and Ireland using the following gas categories Finest Platinum I2H G20 with a governed gas su...

Страница 4: ...e maximum minimum permissible allowable length of the flue system is Horizontal flue terminal Right and Left maximum 2500 mm 99 in Horizontal flue terminal Rear maximum 2000 mm 79 in Horizontal flue t...

Страница 5: ...L SOCKET 3 Fig 3 b Offset vertical flue a measured from the boiler centre line to the centre line of the extension elbow b measured from the centre line of the extension elbow to the underside of the...

Страница 6: ...Supplied By www heating spares co Tel 0161 620 6677 6 EXPLODED DIAGRAM for key no references see spare parts catalogue Drawing amended June 03 4...

Страница 7: ...ater IN Plate Heat Exchanger Overheat Stat DHW out Heating Flow By Pass 3 bar Pressure Relief Valve DOMESTIC HOT WATER MODE AUTOMATIC AIR VENT EXPANSION VESSEL Heating Return PRESSURE GAUGE PUMP Cold...

Страница 8: ...d Use Regulations The appropriate Building Regulations either The Building Regulations The Building Regulations Scotland Building Regulations Northern Ireland The Water Fittings Regulations or Water b...

Страница 9: ...ernal room space or be on the same wall to external air Each air vent communicating with another room or internal space must have a minimum effective area of 362 cm2 56 in2 If the ventilation is direc...

Страница 10: ...UIREMENTS Vessel charge and initial system pressure Total water content of system using 8ltr 1 54gal capacity expansion vessel supplied with appliance For systems having a larger capacity multiply the...

Страница 11: ...PEN POSITION PRESSURE RELIEF VALVE OUTLET TO DRAIN DOMESTIC HOT WATER DOMESTIC COLD WATER PRESSURE REDUCING VALVE IF REQUIRED BS STOP VALVE FIXED SPINDLE MAINS WATER DRAIN COCK AT LOWEST POINT S OF SY...

Страница 12: ...s are achieved Ensure squareness by hanging a plumbline b Mark the position of the wall mounting plate fixing holes 4 Select one from each group Refer to Fig 12 c Mark the position of the flue outlet...

Страница 13: ...ral heating system to the boiler flow and return isolating valves 13 DETERMINING THE POSITION OF THE AIR FLUE DUCT HOLE 14 4 4 SERVICE CONNECTIONS 4 3 MOUNTING THE BOILER 225mm 225mm 95mm 13 b SIDE FL...

Страница 14: ...e an adequate seal The wall liner is a tube diameter 130mm with a wall thickness of 0 8mm a Measure the required flue length as shown in Figure 16 Refer to section 2 5 to determine whether any extensi...

Страница 15: ...ON ON AIR DUCT 767mm EXTENSION MIN OVERLAP 50mm 2in 425mm L 76mm MAX 319mm TOP 17mm 17 AIR FLUE DUCT ASSEMBLY STANDARD DUCT Fits Outside Elbow EXTENSION DUCT S Fits Over Duct STANDARD TERMINAL Fits In...

Страница 16: ...e carton as the appliance are to be used fit the restrictor as follows a Note the position of the flue restrictor ring This is fitted on top of the appliance and is secured by the air pressure switch...

Страница 17: ...ue system towards the boiler to seat the external sealing ring against the outside wall and secure the air duct to the elbow using the two screws provided e Finally use the internal sealing ring to ma...

Страница 18: ...rough the clamping arrangement The cable will be held in position as the plug cover is fitted If a room thermostat is to be fitted remove the red link between L2 and L3 and connect the thermostat acro...

Страница 19: ...em air vents in accordance with normal practice Ensure that all system air vents are closed NOTE The boiler is supplied with a filling loop and fittings 3 Check the system for soundness 4 Check the op...

Страница 20: ...h Ensure that the room thermostat if fitted is calling for heat Turn the clock override switch to the I position Turn the CH temperature control knob to the position The boiler will perform a series...

Страница 21: ...from firing if there is inadequate water flow through the main heat exchanger DHW PRE HEAT DHW Comfort selected With no demand for DHW the boiler will fire periodically for a few seconds to maintain t...

Страница 22: ...lide the burner out of the combustion chamber g Inspect and if necessary clean the main burner ports using a soft brush or vacuum cleaner Do not use a wire brush or any abrasive material Check that th...

Страница 23: ...sembled into the injector Refer to Fig 30 Check that all joints and seals are correctly fitted Note that fan polarity is immaterial a Slacken the screw in the burner pressure test point and connect a...

Страница 24: ...Supplied By www heating spares co Tel 0161 620 6677 22 INTERNAL WIRING DIAGRAMS 7 7 1 FUNCTIONAL FLOW WIRING DIAGRAM...

Страница 25: ...T FINDING In the event of the boiler failing to light refer to the Diagnostics Chart Detailed procedures for replacing faulty components are described in section 9 Parts Replacement For further inform...

Страница 26: ...heir position e Remove the fan assembly 3 screws and withdraw the assembly by lowering and lifting it forwards f Fit the new fan assembly and re assemble in reverse order Ensure that all joints and se...

Страница 27: ...aint re applied to seal it 9 6 AIR PRESSURE SWITCH Refer to Fig 29 a Ensure supply voltage is isolated b Remove the casing front panel and sealed chamber front panel Refer to section 9 3 c Disconnect...

Страница 28: ...ection 9 12 d Remove the two spring clips securing the bypass pipe and pull out the pipe e Remove the two socket screws securing the heat exchanger to the water manifolds and push the heat exchanger d...

Страница 29: ...nion connections and remove the valve d Fit the new valve and re assemble in reverse order e Re commission the system Refer to section 5 9 20 MAIN HEAT EXCHANGER Refer to Fig 29 a Remove the casing fr...

Страница 30: ...MBLY 1 601012 9 DHW FLOWSWITCH Hall effect Sensor 1 500641 10a CH O HEAT THERMISTOR 1 550530 10b DHW THERMISTOR 1 500590 11 MAIN HEAT EXCHANGER 1 450984 12 DHW HEAT EXCHANGER 1 451011 13 PRESSURE RELI...

Страница 31: ...or less For fitting instructions refer to Fig 22 The flue restrictor supplied with the appliance must not be used and should be discarded a Read the installation requirements and flue specifications d...

Страница 32: ...ephone 01787 272800 Sales Direct Line 01787 475557 Fax 01787 474588 Service Helpline 01926 834834 Training 01926 834838 Email sales halsteadboilers co uk or service halsteadboilers co uk or training h...

Отзывы: