e

Explain the function of the boiler overheat thermostat, and how to re-set  it. 
Emphasise that if cut-out persists, the boiler should be turned off and the 
installer or service engineer consulted.

f)

Str

ess the importance of an annual service by a registered heating 

engineer.

g)

The electrical mains supply to the appliance must r

emain ON and the 

ON/OFF switch must be left ON for the frost protection circuit to operate. 

28

FITTING THE CASING P

ANELS

5.7

FROST PROTECTION

5.8

OTHER FEATURES

5.9

USERS INSTRUCTIONS

The appliance is fitted with an over

heat thermostat (integral with the CH

control thermistor). In the event of overheating, the boiler will go to lockout
and the 

Reset

button show steady RED if the er

ror codes are accessed the

LED 4 (Code 0001) will illuminate. Allow the boiler to cool, then press the

Reset

button to clear

.

5.5

IGNITION LOCKOUT

5.6

OVERHEAT THERMOSTAT

In the event of failur

e during an ignition sequence, (5 attempts) the

Reset

LED will show steady RED.  By pr

essing and holding the 

Reset

button 3 seconds the Reset LED will flash RED and LEDs 1 to 4 will

display the error code (0011). To 

Reset

the appliance and initiate a

further ignition attempt, press the 

Reset

button.

NOTE:

In the event of failure during normal running, the Reset LED will

show steady RED.

T

o access the relevant error codes, press the 

Reset

button for thr

ee

seconds. The 

Reset

LED will flash RED.  T

o reset the appliance press the

Reset

button.

The appliance is fitted with a frost protection device. In the event of very
cold conditions, the pump may operate and the boiler light for a few
minutes to protect the appliance and system from potential frost damage.
This can only function if the gas and electricity supplies are maintained and
the ON/OFF switch on the appliance is left ON. (1) The clock can be
switched to the OFF setting.

The following additional features are included in the appliance
specification:

ANTI-CYCLE DEVICE

: When the appliance cycles on its central heating

control thermostat, a slow cycle device operates. The timer (set to 3 mins) is
activated after the end of burn cycle to prevent rapid cycling of the burner.

ANTI PUMP SEIZURE DEVICE:

Pr

oviding that a power supply is maintained and the appliance ON/OFF

switch is ON, the pump will operate for at least 20 seconds every 23 hours
(regardless of heat demand) to prevent pump seizure during periods where
the appliance is not used.

W

ATER FLOW SWITCH:

This device pr

events the burner from firing if there is inadequate water flow

through the main heat exchanger.

DHW PRE-HEA

T:

DHW 

Comfor

t

selected: W

ith no demand for DHW the boiler will fire

periodically for a few seconds to maintain the DHW plate heat exchanger in
a heated condition. This feature will automatically adjust to the user’s habitual
requirements. Thus during long periods of no DHW draw-off, eg overnight, no
pre-heat is provided. DHW 

Economy

selected: No pr

e-heat is provided.

Upon completion of commissioning and testing the system, the installer must
instruct the user in how to operate the appliance by drawing the user's
attention to the following.

a)

Give the 'Users Instr

uctions' to the householder and emphasise their 

responsibilities under the 'Gas Safety (Installation and Use) Regulations or
rules in force.

b) 

Explain and demonstrate the lighting and shutdown pr

ocedures.

c)

Advise the householder on the ef

ficient use of the system, including the 

use and adjustment of all system controls for both CH and DHW.

d)

Advise the user of the pr

ecautions necessary to prevent damage to the 

system, and to the building, in the event of the system remaining 
inoperative during frost conditions.

5.10

BOILER LOGBOOK

A logbook is supplied with this appliance to r

ecord installation and

commissioning details and to make future servicing of the appliance
easier.
This logbook forms part of the industry's Benchmark code of practice for
the installation, commissioning and servicing of central heating systems.
Please ensure that the logbook is fully completed and left with the
customer for future reference, along with Users Instructions and this
Installation and Servicing Instruction manual.

5.11

CONVERSION INSTRUCTIONS

Appliance conversion fr

om one gas group to another is only possible for

category II2H3P appliances; these may be converted between Propane

and natural gas by use of conversion kits. the kits comprise the following.
Propane to Natural Gas - Kit Number: 955095 
• Main Burner Injectors 1.35 mm Ø x 13
• Gas Control Valve
• Boiler Chip Card Nat. Gas
• Flue Restrictor Ring 47 mm Ø
• Data Badge (Nat. Gas)
• Conversion Instructions

Natural Gas to Propane
• Main Burner Injectors 0.9 mm Ø x 13
• Gas Control Valve
• Boiler Chip Card Propane
• Flue Restrictor Ring 43 mm Ø
• Data Badge (Propane)
• Conversion Instructions

Instructions on how to convert the appliance is given in the conversion
instructions supplied with these kits. However, particular attention should
be given to the fitting of flue restrictors and to the use of the Boiler Chip
card.

For further information contact: Halstead Boilers Ltd, Service Help Line,
01926 834 834

FIT BALL STUDS TO

FRONT PANEL

3 HOLES ON
EACH SIDE PANEL
WILL HAVE RUBBER
GROMMETS FITTED
BY THE INSTALLER

19

Содержание Finest Platinum

Страница 1: ...FINEST PLATINUM P R E M I U M P E R F O R M A N C E C O M B I B O I L E R INSTALLATION AND SERVICING INSTRUCTIONS TO BE GIVEN TO THE USER 0086 EC 0087 BO 33 G C Appliance No 47 260 02 Finest Platinum...

Страница 2: ...ator is fitted with lockshield valves normally in the bathroom to allow pump overrun circulation Internal frost protection is fitted as standard equipment The boiler may be used with any certified mai...

Страница 3: ...iance is certified to comply with the requirements of EN 483 and EN 625 for use in GB and IE Great Britain and Ireland using the following gas categories Finest Platinum I2H G20 with a governed gas su...

Страница 4: ...e maximum minimum permissible allowable length of the flue system is Horizontal flue terminal Right and Left maximum 2500 mm 99 in Horizontal flue terminal Rear maximum 2000 mm 79 in Horizontal flue t...

Страница 5: ...L SOCKET 3 Fig 3 b Offset vertical flue a measured from the boiler centre line to the centre line of the extension elbow b measured from the centre line of the extension elbow to the underside of the...

Страница 6: ...Supplied By www heating spares co Tel 0161 620 6677 6 EXPLODED DIAGRAM for key no references see spare parts catalogue Drawing amended June 03 4...

Страница 7: ...ater IN Plate Heat Exchanger Overheat Stat DHW out Heating Flow By Pass 3 bar Pressure Relief Valve DOMESTIC HOT WATER MODE AUTOMATIC AIR VENT EXPANSION VESSEL Heating Return PRESSURE GAUGE PUMP Cold...

Страница 8: ...d Use Regulations The appropriate Building Regulations either The Building Regulations The Building Regulations Scotland Building Regulations Northern Ireland The Water Fittings Regulations or Water b...

Страница 9: ...ernal room space or be on the same wall to external air Each air vent communicating with another room or internal space must have a minimum effective area of 362 cm2 56 in2 If the ventilation is direc...

Страница 10: ...UIREMENTS Vessel charge and initial system pressure Total water content of system using 8ltr 1 54gal capacity expansion vessel supplied with appliance For systems having a larger capacity multiply the...

Страница 11: ...PEN POSITION PRESSURE RELIEF VALVE OUTLET TO DRAIN DOMESTIC HOT WATER DOMESTIC COLD WATER PRESSURE REDUCING VALVE IF REQUIRED BS STOP VALVE FIXED SPINDLE MAINS WATER DRAIN COCK AT LOWEST POINT S OF SY...

Страница 12: ...s are achieved Ensure squareness by hanging a plumbline b Mark the position of the wall mounting plate fixing holes 4 Select one from each group Refer to Fig 12 c Mark the position of the flue outlet...

Страница 13: ...ral heating system to the boiler flow and return isolating valves 13 DETERMINING THE POSITION OF THE AIR FLUE DUCT HOLE 14 4 4 SERVICE CONNECTIONS 4 3 MOUNTING THE BOILER 225mm 225mm 95mm 13 b SIDE FL...

Страница 14: ...e an adequate seal The wall liner is a tube diameter 130mm with a wall thickness of 0 8mm a Measure the required flue length as shown in Figure 16 Refer to section 2 5 to determine whether any extensi...

Страница 15: ...ON ON AIR DUCT 767mm EXTENSION MIN OVERLAP 50mm 2in 425mm L 76mm MAX 319mm TOP 17mm 17 AIR FLUE DUCT ASSEMBLY STANDARD DUCT Fits Outside Elbow EXTENSION DUCT S Fits Over Duct STANDARD TERMINAL Fits In...

Страница 16: ...e carton as the appliance are to be used fit the restrictor as follows a Note the position of the flue restrictor ring This is fitted on top of the appliance and is secured by the air pressure switch...

Страница 17: ...ue system towards the boiler to seat the external sealing ring against the outside wall and secure the air duct to the elbow using the two screws provided e Finally use the internal sealing ring to ma...

Страница 18: ...rough the clamping arrangement The cable will be held in position as the plug cover is fitted If a room thermostat is to be fitted remove the red link between L2 and L3 and connect the thermostat acro...

Страница 19: ...em air vents in accordance with normal practice Ensure that all system air vents are closed NOTE The boiler is supplied with a filling loop and fittings 3 Check the system for soundness 4 Check the op...

Страница 20: ...h Ensure that the room thermostat if fitted is calling for heat Turn the clock override switch to the I position Turn the CH temperature control knob to the position The boiler will perform a series...

Страница 21: ...from firing if there is inadequate water flow through the main heat exchanger DHW PRE HEAT DHW Comfort selected With no demand for DHW the boiler will fire periodically for a few seconds to maintain t...

Страница 22: ...lide the burner out of the combustion chamber g Inspect and if necessary clean the main burner ports using a soft brush or vacuum cleaner Do not use a wire brush or any abrasive material Check that th...

Страница 23: ...sembled into the injector Refer to Fig 30 Check that all joints and seals are correctly fitted Note that fan polarity is immaterial a Slacken the screw in the burner pressure test point and connect a...

Страница 24: ...Supplied By www heating spares co Tel 0161 620 6677 22 INTERNAL WIRING DIAGRAMS 7 7 1 FUNCTIONAL FLOW WIRING DIAGRAM...

Страница 25: ...T FINDING In the event of the boiler failing to light refer to the Diagnostics Chart Detailed procedures for replacing faulty components are described in section 9 Parts Replacement For further inform...

Страница 26: ...heir position e Remove the fan assembly 3 screws and withdraw the assembly by lowering and lifting it forwards f Fit the new fan assembly and re assemble in reverse order Ensure that all joints and se...

Страница 27: ...aint re applied to seal it 9 6 AIR PRESSURE SWITCH Refer to Fig 29 a Ensure supply voltage is isolated b Remove the casing front panel and sealed chamber front panel Refer to section 9 3 c Disconnect...

Страница 28: ...ection 9 12 d Remove the two spring clips securing the bypass pipe and pull out the pipe e Remove the two socket screws securing the heat exchanger to the water manifolds and push the heat exchanger d...

Страница 29: ...nion connections and remove the valve d Fit the new valve and re assemble in reverse order e Re commission the system Refer to section 5 9 20 MAIN HEAT EXCHANGER Refer to Fig 29 a Remove the casing fr...

Страница 30: ...MBLY 1 601012 9 DHW FLOWSWITCH Hall effect Sensor 1 500641 10a CH O HEAT THERMISTOR 1 550530 10b DHW THERMISTOR 1 500590 11 MAIN HEAT EXCHANGER 1 450984 12 DHW HEAT EXCHANGER 1 451011 13 PRESSURE RELI...

Страница 31: ...or less For fitting instructions refer to Fig 22 The flue restrictor supplied with the appliance must not be used and should be discarded a Read the installation requirements and flue specifications d...

Страница 32: ...ephone 01787 272800 Sales Direct Line 01787 475557 Fax 01787 474588 Service Helpline 01926 834834 Training 01926 834838 Email sales halsteadboilers co uk or service halsteadboilers co uk or training h...

Отзывы: