background image

Supplied By www.heating spares.co  Tel. 0161 620 6677

ROUTINE SERVICING

6

29

LOCA

TION OF 

SERVICEABLE 
COMPONENTS

6.1

MAIN BURNER ASSEMBLY

6.2

BURNER INJECTOR

6.3

IGNITION AND DETECTION ELECTRODES

6.4

FAN ASSEMBLY

T

o ensure continued efficient operation of the appliance, it is

recommended that it is checked and serviced as necessary at regular

intervals. The frequency of servicing will depend upon the particular

installation conditions and usage, but in general once a year should

be adequate. It is the law that any service work must be carried out

by a competent person, such as British Gas or other CORGI

registered personnel.
The boiler incorporates a flue sampling point on the top panel in

front of the flue outlet. If the service engineer has suitable equipment

to analyse the flue gas, the plastic cap may be removed and a 6mm

inside diameter sample tube fitted. Check CO

2

/CO values and

compare with figure stated in section 2.4. Do not forget to replace

the plastic cap after use. Before commencing any service operation,

ISOLATE the mains electrical supply, and TURN OFF the gas supply

at the main service cock.
Service the appliance by following the full procedure detailed below:

Refer to Figs. 29 and 30

a)

Remove the casing fr

ont panel. Refer to Fig. 31.

b)

Remove the sealed chamber fr

ont panel (4 screws).

c)

Remove the combustion chamber fr

ont panel (9 screws). Take

care not to damage the insulation.

Do not attempt to light the burner with Front Panel removed.

d)

Remove the two securing scr

ews and lower the controls fascia

panel.

e)

Disconnect the thr

ee leads from the spark and detection

electrodes and disengage the grommets from the combustion

chamber bottom panel.

f)

Remove the 4 scr

ews securing the burner to the gas manifold

and slide the burner out of the combustion chamber.

g)

Inspect, and if necessar

y clean the main burner ports using a soft

brush or vacuum cleaner. Do not use a wire brush or any

abrasive material.

Check that the injectors fitted in the gas manifold are free from dirt and

debris. If necessary, clean the injector orifices carefully using a soft

brush or vacuum cleaner. Do not use a wire brush or any abrasive

material.

It is not necessar

y to remove the injectors.

If ther

e are signs of

injector(s) being blocked please call the Halstead Service Department.

a)

Inspect the ignition and detection electr

odes in situ. If necessary,

clean using a soft brush. If either the electrode or the ceramic

insulation show signs of damage or wear, replace the

electrode(s).

b)

Check that the alignments of the ignition and detection

electrodes are correct. Refer to Fig. 34. Adjust by carefully

bending the tip of the electrode rod whilst supporting the base of

the rod. Do not put any pressure on the ceramic insulation.

a)

Remove combustion chamber fr

ont panel.  Refer to 6.1.

b)

Car

efully disconnect the two electrical leads from the fan.

c)

Disconnect the air pr

essure switch sensing pipes from the fan, 

noting their positions

d)

Remove the fan assembly by unscr

ewing the three screws, 

lowering the assembly and lifting it forwards. 

e)

Inspect the fan assembly (especially the impeller and the venturi) 

for dirt, damage, or signs of wear. If necessary clean the 

impeller and/or venturi using a soft brush or vacuum cleaner. 

Spin the impeller and check that it rotates freely, without noise, 

and without imbalance. If there is any sign of deterioration or 

damage, replace the fan.

COMBUSTION CHAMBER

FRONT PANEL FIXING
SCREWS (9)

AUTO AIR

VENT

FAN ASSEMBLY BASE
PLATE SCREWS

PUMP

GROUP SET

CONTROL 
BOX  

AIR PRESSURE
SWITCH & PIPES

GAS CONTROL VALVE

GAS COCK

PRESSURE RELIEF
VALVE

FAN ASSEMBLY

PRESSURE
GAUGE

OVERHEA

T THERMOSTAT

CONTROL P

ANEL

DETECTION ELECTRODE

BURNER

IGNITION ELECTRODES

• •

20

Содержание Finest Platinum

Страница 1: ...FINEST PLATINUM P R E M I U M P E R F O R M A N C E C O M B I B O I L E R INSTALLATION AND SERVICING INSTRUCTIONS TO BE GIVEN TO THE USER 0086 EC 0087 BO 33 G C Appliance No 47 260 02 Finest Platinum...

Страница 2: ...ator is fitted with lockshield valves normally in the bathroom to allow pump overrun circulation Internal frost protection is fitted as standard equipment The boiler may be used with any certified mai...

Страница 3: ...iance is certified to comply with the requirements of EN 483 and EN 625 for use in GB and IE Great Britain and Ireland using the following gas categories Finest Platinum I2H G20 with a governed gas su...

Страница 4: ...e maximum minimum permissible allowable length of the flue system is Horizontal flue terminal Right and Left maximum 2500 mm 99 in Horizontal flue terminal Rear maximum 2000 mm 79 in Horizontal flue t...

Страница 5: ...L SOCKET 3 Fig 3 b Offset vertical flue a measured from the boiler centre line to the centre line of the extension elbow b measured from the centre line of the extension elbow to the underside of the...

Страница 6: ...Supplied By www heating spares co Tel 0161 620 6677 6 EXPLODED DIAGRAM for key no references see spare parts catalogue Drawing amended June 03 4...

Страница 7: ...ater IN Plate Heat Exchanger Overheat Stat DHW out Heating Flow By Pass 3 bar Pressure Relief Valve DOMESTIC HOT WATER MODE AUTOMATIC AIR VENT EXPANSION VESSEL Heating Return PRESSURE GAUGE PUMP Cold...

Страница 8: ...d Use Regulations The appropriate Building Regulations either The Building Regulations The Building Regulations Scotland Building Regulations Northern Ireland The Water Fittings Regulations or Water b...

Страница 9: ...ernal room space or be on the same wall to external air Each air vent communicating with another room or internal space must have a minimum effective area of 362 cm2 56 in2 If the ventilation is direc...

Страница 10: ...UIREMENTS Vessel charge and initial system pressure Total water content of system using 8ltr 1 54gal capacity expansion vessel supplied with appliance For systems having a larger capacity multiply the...

Страница 11: ...PEN POSITION PRESSURE RELIEF VALVE OUTLET TO DRAIN DOMESTIC HOT WATER DOMESTIC COLD WATER PRESSURE REDUCING VALVE IF REQUIRED BS STOP VALVE FIXED SPINDLE MAINS WATER DRAIN COCK AT LOWEST POINT S OF SY...

Страница 12: ...s are achieved Ensure squareness by hanging a plumbline b Mark the position of the wall mounting plate fixing holes 4 Select one from each group Refer to Fig 12 c Mark the position of the flue outlet...

Страница 13: ...ral heating system to the boiler flow and return isolating valves 13 DETERMINING THE POSITION OF THE AIR FLUE DUCT HOLE 14 4 4 SERVICE CONNECTIONS 4 3 MOUNTING THE BOILER 225mm 225mm 95mm 13 b SIDE FL...

Страница 14: ...e an adequate seal The wall liner is a tube diameter 130mm with a wall thickness of 0 8mm a Measure the required flue length as shown in Figure 16 Refer to section 2 5 to determine whether any extensi...

Страница 15: ...ON ON AIR DUCT 767mm EXTENSION MIN OVERLAP 50mm 2in 425mm L 76mm MAX 319mm TOP 17mm 17 AIR FLUE DUCT ASSEMBLY STANDARD DUCT Fits Outside Elbow EXTENSION DUCT S Fits Over Duct STANDARD TERMINAL Fits In...

Страница 16: ...e carton as the appliance are to be used fit the restrictor as follows a Note the position of the flue restrictor ring This is fitted on top of the appliance and is secured by the air pressure switch...

Страница 17: ...ue system towards the boiler to seat the external sealing ring against the outside wall and secure the air duct to the elbow using the two screws provided e Finally use the internal sealing ring to ma...

Страница 18: ...rough the clamping arrangement The cable will be held in position as the plug cover is fitted If a room thermostat is to be fitted remove the red link between L2 and L3 and connect the thermostat acro...

Страница 19: ...em air vents in accordance with normal practice Ensure that all system air vents are closed NOTE The boiler is supplied with a filling loop and fittings 3 Check the system for soundness 4 Check the op...

Страница 20: ...h Ensure that the room thermostat if fitted is calling for heat Turn the clock override switch to the I position Turn the CH temperature control knob to the position The boiler will perform a series...

Страница 21: ...from firing if there is inadequate water flow through the main heat exchanger DHW PRE HEAT DHW Comfort selected With no demand for DHW the boiler will fire periodically for a few seconds to maintain t...

Страница 22: ...lide the burner out of the combustion chamber g Inspect and if necessary clean the main burner ports using a soft brush or vacuum cleaner Do not use a wire brush or any abrasive material Check that th...

Страница 23: ...sembled into the injector Refer to Fig 30 Check that all joints and seals are correctly fitted Note that fan polarity is immaterial a Slacken the screw in the burner pressure test point and connect a...

Страница 24: ...Supplied By www heating spares co Tel 0161 620 6677 22 INTERNAL WIRING DIAGRAMS 7 7 1 FUNCTIONAL FLOW WIRING DIAGRAM...

Страница 25: ...T FINDING In the event of the boiler failing to light refer to the Diagnostics Chart Detailed procedures for replacing faulty components are described in section 9 Parts Replacement For further inform...

Страница 26: ...heir position e Remove the fan assembly 3 screws and withdraw the assembly by lowering and lifting it forwards f Fit the new fan assembly and re assemble in reverse order Ensure that all joints and se...

Страница 27: ...aint re applied to seal it 9 6 AIR PRESSURE SWITCH Refer to Fig 29 a Ensure supply voltage is isolated b Remove the casing front panel and sealed chamber front panel Refer to section 9 3 c Disconnect...

Страница 28: ...ection 9 12 d Remove the two spring clips securing the bypass pipe and pull out the pipe e Remove the two socket screws securing the heat exchanger to the water manifolds and push the heat exchanger d...

Страница 29: ...nion connections and remove the valve d Fit the new valve and re assemble in reverse order e Re commission the system Refer to section 5 9 20 MAIN HEAT EXCHANGER Refer to Fig 29 a Remove the casing fr...

Страница 30: ...MBLY 1 601012 9 DHW FLOWSWITCH Hall effect Sensor 1 500641 10a CH O HEAT THERMISTOR 1 550530 10b DHW THERMISTOR 1 500590 11 MAIN HEAT EXCHANGER 1 450984 12 DHW HEAT EXCHANGER 1 451011 13 PRESSURE RELI...

Страница 31: ...or less For fitting instructions refer to Fig 22 The flue restrictor supplied with the appliance must not be used and should be discarded a Read the installation requirements and flue specifications d...

Страница 32: ...ephone 01787 272800 Sales Direct Line 01787 475557 Fax 01787 474588 Service Helpline 01926 834834 Training 01926 834838 Email sales halsteadboilers co uk or service halsteadboilers co uk or training h...

Отзывы: