RE 15345-WA, Version 11.2022, Bosch Rexroth AB
Installation |
Drive system Hägglunds Fusion 39/72
7.6.4 Voltage equalization
External grounding
The Hägglunds drive system must be connected to external grounding for voltage
equalization.
The grounding point of the Hägglunds drive system is on the side of the frame to
a M8 bolt. Minimum required cable area for equalization connection is 10 mm
2
(0.016 in
2
)
.
Fig. 20:
Grounding point
42637
7.6.5 Cabinet heater (optional)
Heating capacity
1
Operation voltage
Max current
Setting range
2
1200 W
AC 230 V, 50/60Hz
13.0 A
0 to 60 °C (32° to 140°F)
1
At 20 °C (68°F) ambient temperature
2
Switching difference 7°C ± 4°C (12.6°F ± 7°F).
Standard settings from Hägglunds 10°C (50°F)
Connect the cables on the screw terminals inside the cabinet heater. Tightening
torque
0.8 Nm.(7.1 lbf ·in)
The device must be connected to mains via an all-pole disconnecting device (with
contact gap of at least 3 mm in the switched-off state).