Specifications
A textual string containing name of a Relay Port.
epc8226PortState
.58.1.3.1.2.1.3.x
INTEGER
RW
current state of a Relay Port
epc8226PortSwitchCount
.58.1.3.1.2.1.4.x
Integer32
RO
The total number of switch actions ocurred on a Relay Port. Does not
count switch commands which will not switch the ralay state, so just real
relay switches are displayed here.
epc8226PortStartupMode
.58.1.3.1.2.1.5.x
INTEGER
RW
set Mode of startup sequence (off, on , remember last state)
epc8226PortStartupDelay
.58.1.3.1.2.1.6.x
Integer32
RW
Delay in sec for startup action
epc8226PortRepowerTime
.58.1.3.1.2.1.7.x
Integer32
RW
Delay in sec for repower port after switching off
epc8226PortResetDuration
.58.1.3.1.2.1.8.x
Integer32
RW
Delay in sec for turning Port on again after Reset action
epc8226Buzzer
.58.1.3.10.0
Integer32
RW
turn Buzzer on and off
epc8226ActivePowerChan
.58.1.5.1.1.0
Unsigned32
RO
Number of suppported Power Channels.
epc8226PowerIndex
.58.1.5.1.2.1.1.x
Integer32
RO
Index of Power Channel entries
epc8226ChanStatus
.58.1.5.1.2.1.2.x
Integer32
RO
0 = data not active, 1 = data valid
epc8226AbsEnergyActive
.58.1.5.1.2.1.3.x
Gauge32
RO
Absolute Active Energy counter.
epc8226PowerActive
.58.1.5.1.2.1.4.x
Integer32
RO
Active Power
epc8226Current
.58.1.5.1.2.1.5.x
Gauge32
RO
Actual Curent on Power Channel.
epc8226Voltage
.58.1.5.1.2.1.6.x
Gauge32
RO
Actual Voltage on Power Channel
epc8226Frequency
.58.1.5.1.2.1.7.x
Gauge32
RO
Frequency of Power Channel
epc8226PowerFactor
.58.1.5.1.2.1.8.x
Integer32
RO
Power Factor of Channel between -1.0 and 1.00
epc8226Pangle
.58.1.5.1.2.1.9.x
Integer32
RO
Phase Angle between Voltage and L Line Current between -180.0 and
180.0
epc8226PowerApparent
.58.1.5.1.2.1.10.x
Integer32
RO
L Line Mean Apparent Power
epc8226PowerReactive
.58.1.5.1.2.1.11.x
Integer32
RO
L Line Mean Reactive Power
epc8226AbsEnergyReactive
.58.1.5.1.2.1.12.x
Gauge32
RO
Absolute Reactive Energy counter.
epc8226AbsEnergyActiveReset-
table
.58.1.5.1.2.1.13.x
Gauge32
RW
Resettable Absolute Active Energy counter. Writing '0' resets all reset-
table counter.
epc8226AbsEnergyReactiveReset-
table
.58.1.5.1.2.1.14.x
Gauge32
RO
Resettable Absolute Reactive Energy counter.
epc8226ResetTime
.58.1.5.1.2.1.15.x
Gauge32
RO
Time in seconds since last Energy Counter reset.
epc8226ForwEnergyActive
.58.1.5.1.2.1.16.x
Gauge32
RO
Forward Active Energy counter.
epc8226ForwEnergyReactive
.58.1.5.1.2.1.17.x
Gauge32
RO
Forward Reactive Energy counter.
epc8226ForwEnergyActiveReset-
table
.58.1.5.1.2.1.18.x
Gauge32
RO
Resettable Forward Active Energy counter.
epc8226ForwEnergyReactiveRe-
settable
.58.1.5.1.2.1.19.x
Gauge32
RO
Resettable Forward Reactive Energy counter.
epc8226RevEnergyActive
.58.1.5.1.2.1.20.x
Gauge32
RO
Reverse Active Energy counter.
epc8226RevEnergyReactive
.58.1.5.1.2.1.21.x
Gauge32
RO
Reverse Reactive Energy counter.
epc8226RevEnergyActiveReset-
table
.58.1.5.1.2.1.22.x
Gauge32
RO
Resettable Reverse Active Energy counter.
epc8226RevEnergyReactiveReset-
table
.58.1.5.1.2.1.23.x
Gauge32
RO
Resettable Reverse Reactive Energy counter.
epc8226LineSensorName
.58.1.5.1.2.1.100.x
OCTETS
RW
A textual string containing name of a Line Sensor
epc8226OVPIndex
.58.1.5.2.1.1.x
Integer32
RO
None
Содержание Expert Power Control 8221 Series
Страница 2: ...2 Expert Power Control 8221 8226 2021 GUDE Systems GmbH ...
Страница 5: ...Device Description ...
Страница 13: ...13 Expert Power Control 8221 8226 2021 GUDE Systems GmbH Device Description ...
Страница 14: ...Operating ...
Страница 24: ...Configuration ...
Страница 50: ...Specifications ...
Страница 91: ...Support ...