28
Expert Power Control 8221/8226
© 2021 GUDE Systems GmbH
Configuration
The option Repeat reset on booting host after x ping timeout has the following pit-
fall: If a server, that is connected to the monitored Port is in need for a long boot pro-
cess (e.g. it is doing a file system check), the server would probably exceed the trip-
ping time of the watchdog. The server would be switched off and on again, and the file
system check is restarted. This would be repeated endlessly.
count PING requests as unreplied when ethernet link down: If the Ethernet link of the
device is not active, watchdog monitoring is not possible and the watchdog function is
not activated. If this option is activated, a watchdog is also triggered if the Ethernet link
is down.
3.2
Ethernet
3.2.1
IP Address
Hostname: Here you can enter a name with up to 63 characters. This name will be
used for registration on the DHCP server.
Special characters and umlauts can cause problems in the network.
IPv4 Address: The IP address of the device.
IPv4 Netmask: The network mask used in the network.
IPv4 Gateway address: The IP address of the gateway.
IPv4 DNS address: The IP address of the DNS server.
Use IPv4 DHCP: Select "yes" if the TCP/IP settings should be obtained directly from
the DHCP server: When the function is selected, each time the device powers up it is
checked if a DHCP server is available on the network. If not, the last used TCP/IP set-
ting will be used further.
Содержание Expert Power Control 8221 Series
Страница 2: ...2 Expert Power Control 8221 8226 2021 GUDE Systems GmbH ...
Страница 5: ...Device Description ...
Страница 13: ...13 Expert Power Control 8221 8226 2021 GUDE Systems GmbH Device Description ...
Страница 14: ...Operating ...
Страница 24: ...Configuration ...
Страница 50: ...Specifications ...
Страница 91: ...Support ...