12
Expert Power Control 8221/8226
© 2021 GUDE Systems GmbH
Device Description
Product Name
7101
7104-1
7105-1
7106-1
Calibrated
Sensor
-
7104-2
7105-2
7106-2
Cable length
Connector
RJ45
RJ45
RJ45
RJ45
temperature range
-20°C to +80°C at
±2°C (maximum)
and ±1°C (typical)
-20°C to +80°C at
±2°C (maximum)
and ±1°C (typical)
-20°C to +80°C at
±2°C (maximum)
and ±1°C (typical)
-20°C to +80°C at
±2°C (maximum)
and ±1°C (typical)
air humidity range
(non-condensing)
-
-
0-100%, ±3%
(maximum) and
±2% (typical)
0-100%, ±3%
(maximum) and
±2% (typical)
air pressure range
(full)
-
-
-
± 1 hPa (typical)
at 300 ... 1100
hPa, 0 ... +40 °C
air pressure range
(ext)
-
-
-
± 1.7 hPa (typical)
at 300 ... 1100
hPa, -20 ... 0 °C
Protection
IP68
-
-
-
Product Name
7201
7202
Cable length
-
-
Connector
RJ45
RJ45
temperature range
-20°C to +80°C at ±2°C (max-
imum) and ±1°C (typical)
-20°C to +80°C at ±2°C (max-
imum) and ±1°C (typical)
air humidity range
(non-condensing)
-
0-100%, ±3% (maximum) and
±2% (typical)
The sensors are automatically detected after connect. This is indicated by the green
LED on the sensor port that is lit permanently.
The sensor values are displayed at
the "Control Panel" web page:
A click on the link in the "Name" column opens the display of the Min and Max values.
The values in a column can be reset using the "Reset" button. The "Reset" button in
the name column deletes all stored Min and Max values.
Содержание Expert Power Control 8221 Series
Страница 2: ...2 Expert Power Control 8221 8226 2021 GUDE Systems GmbH ...
Страница 5: ...Device Description ...
Страница 13: ...13 Expert Power Control 8221 8226 2021 GUDE Systems GmbH Device Description ...
Страница 14: ...Operating ...
Страница 24: ...Configuration ...
Страница 50: ...Specifications ...
Страница 91: ...Support ...