![Gude Expert Power Control 8221 Series Скачать руководство пользователя страница 47](http://html.mh-extra.com/html/gude/expert-power-control-8221-series/expert-power-control-8221-series_manual_2277613047.webp)
47
Expert Power Control 8221/8226
© 2021 GUDE Systems GmbH
Configuration
side the range "below max value", the action defined for "below max value" is per-
formed. In the case of device start, configuration or plug-in of the sensor, the actions
corresponding to the range in which the current temperature is located are switched.
Example with "Maximum value" of 65 °C, "Minimum value" of 25 °C and hysteresis of 3
°C. The dotted line shows the hysteresis.
Actions during configuration, device start or plugging in the sensor (for given example):
actual temperature
during configuration
actions
70 °C
Port A1 Off (above max) + Port A2 On (above min)
45 °C
Port A1 On (below max) + Port A2 On (above min)
20 °C
Port A1 On (below max) + Port A2 Off (below min)
Action matrix during operation when limit values are exceeded (for given example):
to "above max" to "below max" to "above min" to "below min"
from "above
max"
-
A1 On
A1 On
A1 On + A2 Off
from "below max"
A1 Off
-
-
A2 Off
from "above min"
A1 Off
-
-
A2 Off
from "below min" A1 Off + A2 On
A2 On
A2 On
-
Only the switching operations for which actions have been defined, are triggered. If
no "On" or "Off" action is defined for a port, the port can never reach this state by ex-
ceeding sensor values. Unless it is the initial state.
Содержание Expert Power Control 8221 Series
Страница 2: ...2 Expert Power Control 8221 8226 2021 GUDE Systems GmbH ...
Страница 5: ...Device Description ...
Страница 13: ...13 Expert Power Control 8221 8226 2021 GUDE Systems GmbH Device Description ...
Страница 14: ...Operating ...
Страница 24: ...Configuration ...
Страница 50: ...Specifications ...
Страница 91: ...Support ...