GUARDIAN SCC-40
Issue (Auto VI) & V3.6t 07/12/00
DIFFERENTIALS Cont’d
Display
Window
‘type’
selection
‘view’
selection
Settings
unit
Actual
Setting
Default
Setting
Min
Max
SUCTION
DIFF
HIGH TRIP
high-trip suction superheat (Suction
actual temp T1--Suction equivalent temp
P1)
After FIXED 10min timer.
°
C
-40c
100c
FILTER
DIFF
HIGH TRIP
High Trip Filter Differential
IF PUMP & FStd Selected
(Filter Inlet Press P4 – Manifold oil
pressure Press P3)
IF PUMP & Fdis Selected
(Filter inlet Press P2 Discharge—Oil
Pump inlet Press P4)
If No-P,FStd,SCC30/35
(Filter inlet Press P4—Oil Press P3)
After FIXED 2min timer
bar
0.0
20.0
Display
Window
‘type’
selection
‘view’
selection
Settings
unit
Actual
Setting
Default
Setting
Min
Max
TIMERS
SUCTION
TIMERS
SETPOINT
stage up delay (time @ 100%
before allowing next compressor to
start)
(u)
mins
0.1u
12.5u
DISCHARGE
TIMERS
SETPOINT
stage down delay (time @
minimum load or 50% if in slide
balance mode before stopping)
Set at 10.0 = none,
NO STOP AT MINIMUM,
MANUAL STOP ONLY.
N.B. To exit
none
setting =
Discharge, Timer, Setpoint,
Lower, Accept.
(d)
mins
0.1d
10.0d
none
OIL
TIMERS
SETPOINT
pump pre-lube delay ( pump run
time before compressor starts)
(p)
mins
0.2P
5.0P
FILTER
TIMERS
SETPOINT
pump delay after compressor
stops until
at-minimum
received
(o)
mins
0.0o
5.0o
CAPACITY
TIMERS
SETPOINT
slide load delay (interval between
pulses when control within 0.3b)
mins
0.1
5.0
LOAD
TIMERS
SETPOINT
minimum delay after stop before
allowing restart
mins
0.3
12.5
CALIBRATION
4-20mA transducers are calibrated at the factory and should not need to be calibrated
at site.
Before attempting Pressure Calibration, please contact Guardian Electronics Ltd.,
Pressure transducers are set for a range of –1 to 24 Barg. (0-25 Bara)
4mA = -1 Barg,
17.44mA = 20 Barg,
CAUTION, Do not press the accept button if during calibration the display reads
–1.3Barg, as this is an out of range setting and will result in a permanent loss of
calibration.
Содержание SCC 25
Страница 12: ...Page 12 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Consultant Format SCC40 Std ...
Страница 51: ...Page 51 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Auto VI Drawing ...
Страница 52: ...Page 52 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Auto VI Wallbox Wiring ...
Страница 73: ...Page 73 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 SCC 40 Enclosure wiring for trips negative ...
Страница 74: ...Page 74 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 SCC 40 Enclosure wiring for trips positive ...
Страница 76: ...Page 76 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Standard Wallbox Internal wiring ...
Страница 77: ...Page 77 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Standard SCC 40 Drawing ...