Page 57
GUARDIAN SCC-40
Issue (Auto VI) & V3.6t 07/12/00
frigeration input state
for refrigeration ON
yyyy
YYYY=rPos
rnEg
Trip input signal state to
trip
yyyy
YYYY=tPos
tnEg
Refrigeration gas type
yyyy
Refrigeration gas type for superheat
calculations
YYYY=r22
nH3
404A
Filter Differential
yyyy
Filter Position Relative To Pump
YYYY=FStd
Filter Standard (Filter After pump )
FdiS
Filter Discharge (Filter Before Pump )
Port Settings
Note Port is only used on early software versions, all later versions are fixed at a 9600 Baud
rate and ‘Port Settings’ is not used
SUCTION
OIL
==SE tUp=
Press
“
@
next
”
to sequence through Setup selections
DISCHARGE
FILTER
Press
“
@
raise
”
or
“
@
lower
”
to change settings
==== Port
Press
“
@
accept
”
to accept settings
Baud rate
YYYY
YYYY = 9600
Baud rate settings for RS485 highway
4800
communications
2400
1200
Analog
SUCTION
OIL
==SE tUp=
Press
“
@
next
”
to sequence through Setup selections
DISCHARGE
FILTER
Press
“
@
raise
”
or
“
@
lower
”
to change settings
==== AnAL
Press
“
@
accept
”
to accept settings
Pressure transducer
type
P=nn
nn = 0 to 255 P=00 0-100mV
P=04 4-20mA
Slide voltage range
C=nn
nn = 0 to 100 C=00 0-10Vdc
C=05 is normal setting
Current transformer
rating
tnnn
nnn = 10 to 990 Amps
Maximum rated
motor load
rnnn
nnn = 10 to 990 Amps
Содержание SCC 25
Страница 12: ...Page 12 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Consultant Format SCC40 Std ...
Страница 51: ...Page 51 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Auto VI Drawing ...
Страница 52: ...Page 52 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Auto VI Wallbox Wiring ...
Страница 73: ...Page 73 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 SCC 40 Enclosure wiring for trips negative ...
Страница 74: ...Page 74 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 SCC 40 Enclosure wiring for trips positive ...
Страница 76: ...Page 76 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Standard Wallbox Internal wiring ...
Страница 77: ...Page 77 GUARDIAN SCC 40 Issue Auto VI V3 6t 07 12 00 Standard SCC 40 Drawing ...